User Constant Settings and Functions
5.2.2 Position Reference
5 -20
Pn200.1
Setting
Description
Clear Timing
0
Clears the error counter when the CLR
signal goes high.
Error pulses do not accumulate as long
as the signal remains high.
High
CLR
(CN1-15)
Cleared state
1
Clears the error counter on the rising
edge of the CLR signal.
Clears the error counter only once on
the rising edge of the CLR signal.
Cleared only once at this point.
CLR
(CN1-15)
High
2
Clears the error counter when the CLR
signal goes low.
Error pulses do not accumulate as long
as the signal remains low.
Low
CLR
(CN1-15)
Cleared state
3
Clears the error counter on the falling
edge of the CLR signal.
Clears the error counter only once on
the falling edge of the CLR signal.
CLR
(CN1-15)
Low
Cleared only once at this point.