2-2 Connecting the Power Supply
2-2
Connecting the Power Supply
2-2-1 Power supply
Type and Item
DRCX-0505
DRCX-0510
DRCX-0520
DRCX-1005
DRCX-1010
DRCX-1020
DRCX-2005
DRCX-2010
DRCX-2020
No. of phases
Single-phase
Single-phase
Single-phase
Single-phase
Single-phase
Single-phase
Single-phase
Single-phase
Single-phase
Frequency
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
Max. power consumption
500VA or less
700VA or less
1100VA or less
700VA or less
900VA or less
1300VA or less
1100VA or less
1300VA or less
1600VA or less
Power supply voltage
AC100 to 115/200 to 230V
±
10%
AC100 to 115/200 to 230V
±
10%
AC100 to 115/200 to 230V
±
10%
AC100 to 115/200 to 230V
±
10%
AC100 to 115/200 to 230V
±
10%
AC200 to 230V
±
10%
AC100 to 115/200 to 230V
±
10%
AC200 to 230V
±
10%
AC200 to 230V
±
10%
c
CAUTION
If the power supply voltage drops below the above range during operation, the alarm circuit will work and return
the controller to the initial state the same as just after power-on, or stop operation. To avoid this problem, use a
regulated power supply with voltage fluctuations of less than
±
10%.
Since the controller uses a capacitor input type power supply circuit, a large inrush current flows when the
power is turned on. Do not use fast-blow circuit breakers and fuses. For the same reason, avoid turning the
power off and on again repeatedly in intervals of less than 10 seconds. This could harm the main circuit
elements in the controller.