Manual Ozone Generating System
SMOevo
PLUS
System Description
Manual_SMOevoPLUS_eng_01.2019.doc
page 63 of 179
5.5 Process Control
5.5.1 Process Values
mO3=cO3 x VG
m
O3
:
Ozone mass(g/h)
The produced ozone mass is the product of the gas volume flow and the
ozone concentration:
c
O3
:
Ozone concentration (g/Nm³ (NTP))
The ozone mass per norm cubic meter depends on the set converter output
and the set gas volume flow.
V
G
:
Gas volume flow (Nm³/h (NTP))
The gas volume flow in norm cubic meter per hour is adjustable by the
motor control valve. (03.0.15) via PLC.
5.5.2 System Control Modes
5.5.2.1 Control of Power / Gas Flow
The setpoints Converter Power (0 to 100%) and Gas Flow (0 to x Nm³/h) must be preset.
The Required Ozone Mass is then generated according to the nominal capacity of the
SMOevo
PLUS
system.
Refer to Chapter Operating Data.