Manual Ozone Generating System
SMOevo
PLUS
Operation
Manual_SMOevoPLUS_eng_01.2019.doc
page 106 of 179
Production Mode
Dose Control
With the Dose Control, an Ozone Dose per m³/h process water
flow is specified as the main setpoint.
By multiplying the Ozone Dose by the process water flow, the
Required Ozone Mass is obtained.
With this control mode, in addition to the main setpoint Ozone Dose, another constant setpoint
must be specified: Ozone Concentration or Gas Flow Generator.
Depending on the Required Ozone Mass, the non-constant setpoint is changed variably in order
to produce the Required Ozone Mass. The Process Water Flow is the reference variable for
determining the required mass.
Signal
(Setpoint)
Local
Remote
(Hardwired)
Remote
(Network)
Remote
(Wedecontrol)
Gas Flow
Generator
X
-
X
X
Ozone
Concentration
X
-
X
X
Ozone Dose
X
-
X
X
Process Water
Flow
X
X
4W20 mA = 0WX
m³/h Process Water
Flow
X
X