5.3.5 Subassembly 34: Ambient air Monitoring
34.1.10
Ozone
sensor
The safety equipment of the ozone system includes the
ambient air monitor 34.1.10. The ambient air sensor is
installed at a place where the highest ozone concentration is
expected in case of a malfunction.
The ambient air sensor has a built in self test function for daily
checking the functionality of the sensor. Sensor replacement
is recommended every six months.
Refer to Chapter
Maintenance Schedule and the Appentix
Default limit values are as follows
0.1ppm: the PLC generates a warning message.
0.3 ppm: alarm message. The PLC shuts down the system, a
visual and acoustic alarm is triggered, and the ventilation
system is activated.
0.5 ppm: shutdown via relay contact.
Refer to Chapter Safety.