Manual Ozone Generating System
SMOevo
PLUS
System Description
Manual_SMOevoPLUS_eng_01.2019.doc
page 49 of 179
Option: Feed gas PSA and air
01.1.80
Dew point
sensor
Monitors the dew point of the inlet air(set point -70°C atm)
01.1.82
Ball valve
To isolate valves for maintenance or service purposes.
01.1.84
Solenoid
valve
In case of a bad dew point (> -56°C atm) the components
upstream the dew point sensor are purged with the feed gas
air via the solenoid valve until the correct dew point is
reached.
01.1.85
Flow meter
Option Air: Measures the gas volume flow during purging
phase until the correct dew point is reached
01.1.86
Silencer
Option Air: Reduces the noise of exiting feed gas during
purging phase in case of bad dew point.
01.1.88
Flow meter
Option PSA: Measures the gas volume flow during purging
phase until the correct dew point is reached
In contrast to option feed gas air, the feed gas PSA must not be discharged within the
operating rooms. PSA must be discharged as far as to the open air,
refer to Chapter
Responsibilities of the Owner / Operator, Safety Measures
. The position of the gas outlet must be
at least 3 m above the ground level.