Troubleshooting
Manual_SMOevoPLUS_eng_01.2019.doc
page 140 of 179
Message
No.
Message shown on the display
Description /
Possible Cause
Countermeasures
12
SYS:DI1.3 Alarm overload PSU
Current consumption too high.
Incorrect limit value.
Motor protective circuit breaker
defective.
Check input voltage.
Check limit value.
Check motor protective circuit
breaker.
Contact regional Wedeco Service.
Refer to Chapter Contact Addresses.
13
SYS:DI1.4 Alarm overload PSU / Overload
air condition
Current consumption too high.
Incorrect limit value.
Motor protective circuit breaker
defective.
Overload Rittal air condition units.
Eco mode activated on the Rittal
air-condition unit.
Check input voltage.
Check limit value.
Check motor protective circuit
breaker.
Check air condition.
Activate Eco mode on the Rittal air-
condition unit,
refer to manufacturer
manual
.
Contact regional Wedeco customer
service.
Refer to Chapter Contact
Addresses.
14
SYS:DI1.5 Alarm fault external auxiliary
Fault message from external
auxiliary.
Cable break.
Incorrect wiring.
Check cables and connections.
Refer to manufacturer’s manual
.