5.3.1 Subassembly 01: Gas Supply
01.1.30
Ball valve
Gas supply is carried out via a ball valve which must be
fully open during normal operation.
01.1.35
Fine filter
Prevents particles >0.1 µm from entering and damaging
the generator and the valves.
01.1.40
Pressure
regulator
Keeps the operation pressure constant if feed gas
pressure varies within a certain range.
03.1.03
Ball valve
Can be used for the option Ozone Monitor (M1).
01.1.50
Safety
Pressure
Limiter
Combination
Two pressure limiters with integrated pressure transmitter.
Via the analog signal of the pressure transmitter, the PLC
receives the current pressure in the gas inlet. Warning and
switch-off points for exceeding or falling below certain
pressures are stored in the PLC. When the shutdown
points are reached, the system will be switched off via the
PLC.
A message is displayed when the warning points are
reached.
Pressure
Gas Inlet
Description*
Delay
Time
≥3.0 bar (g)
Max. switch-off point
warning message disappears
alarm message appears
→ after 1 sec: system shuts down
1 s
2.7 bar (g)
Max. warning value
≥ 2 .7 bar(g) and < 3 bar(g)
warning message appears after 5 sec
< 2.7 bar(g) warning message disappears
5 s