ROTARY INDEXING TABLE CONTROLLER
EF2...B
INSTALLATION |
6.2 Power Module PM240-2; frame size FSA / FSB
6.2.4.3 Power mains connection 3AC 380 V - 480 V / 2.2 - 3.0 kW
Cyclical switching of the supply voltage is not allowed. After each shutdown, wait five
minutes before switching it on again.
The plug connections are located on the bottom side of the power module.
Fig. 35: Power mains connection 3AC 380 V - 480 V / 2.2 - 3.0 kW
Name
Power mains connection plug
Release lever
L1
External conductor L1
L2
External conductor L2
L3
External conductor L3
PE
Protective ground
Class J UL safety fuses
Rated current
10 A (2.2 kW) / 12 A (3.0 kW)
Safety fuses NH
Rated current
10 A (2.2 kW) / 16 A (3.0 kW)
Screw terminals
Cross-section
Tightening torque
Stripping length
1.5 to 6.0 mm
2
0.6 mm
8.0 mm
1
4
1