b) An overspeeding engine is hard to stop. Therefore, check regularly the
adjustment of the control mechanism (the injection pump rack positions)
1) the stop lever being in stop position or the overspeed trip device being
tripped and the speed governor at maximum fuel admission.
2) the stop lever and the overspeed trip being in work position and the speed
governor in stop position.
This control should be done always when the control mechanism or the
injection pumps have been touched.
22.3
08.2
Emergency operation
08.2.1 Operation with defective air cooler(s)
If the water tubes of an air cooler are defective, the cooling water
may enter the cylinders. If water or water mist flows out of the
drain pipe at the bottom of the cooler housing, check whether it
is raw water or condensate. If condensate, reduce cooling (see
chapter 03, Fig 03-1). If raw water, stop the engine as soon as
possible and fit a spare cooler.
If no spare cooler is available, the following can be done as an
emergency solution:
1 Dismantle the cooler for repair
and blank off the opening
in the charge air cooler housing. Shut off water supply and
return pipes. Repair the cooler, e.g. by plugging the leaking
tubes.
2 If there is not time enough to remove the defective
cooler
and repair it, shut off water supply and return pipes.
Note!
This will influence on the water flow to the tube oil cooler and
the tube oil cooler temperature will increase
3 Operating with a partially plugged, shut-down or re-
moved air cooler.
Engine output must be limited so that the
normal full load exhaust temperatures are not exceeded.
The turbocharger may surge before the admissible exhaust
temperatures are reached. In such a case, engine load must be
reduced further to avoid continuous surging.
08.2.2 Operation with defective turbocharger(s)
A defective turbocharger is to be treated in accordance with the
service instructions given in the turbocharger instruction book
(blocking of rotor etc.).
If one turbocharger on a V-engine is defective and must be
blocked, the other charger should be blocked too. The air connec-
tion between the charger and the air coolers should be removed
and the engine will operated as a naturally aspirated engine.
22-9601
Operating Troubles, Emergency Operation
08
VASA 22
08 - 5
Summary of Contents for Vasa R22
Page 14: ...Appendix B Welding Precautions 200147 00 4...
Page 42: ...02 Fuel Lubricating Oil Cooling Water 22 9601 02 22 VASA 22...
Page 60: ...03 Start Stop and Operation 22 9632 03 12 VASA 22...
Page 72: ...04 Maintenance Schedule 22 9845 III 04 12 MD HF...
Page 92: ...06 II Adjustments Clearances and Wear limits 22 9601 06 6 VASA 22...
Page 116: ...08 Operating Troubles Emergency Operation 22 9601 08 8 VASA 22...
Page 144: ...11 Crank Mechanism 22 9601 11 18 VASA 22...
Page 156: ...12 Cylinder Head with Valves 22 9601 12 12 VASA 22...
Page 164: ...13 Camshaft Driving Gear 22 9601 13 8 VASA 22...
Page 172: ...14 Valve Mechanism and Camshaft 22 9601 14 8 VASA 22...
Page 183: ...22 200520 Turbocharging and Air Cooling 15 VTR Turbocharger 15 11...
Page 189: ...15 III Turbocharging and Air Cooling 22 8604 15 6 VTR 161 251 Turbochargers...
Page 209: ...17 Fuel system 22 9601 17 8 VASA 22...
Page 229: ...18 Lubricating Oil System 22 9601 18 20 VASA 22...
Page 247: ...19 Cooling Water System 22 9601 19 18 VASA 22...
Page 261: ...21 Starting Air System 22 9601 21 10 VASA 22...