3 The valve is jamming.
Clean the valve.
c)
Too low temperature at high load
1 Defective thermostatic element(s)
(the element(s) will
not go back to cold position).
2 Jamming valve.
Clean the valve.
3 The valve is not closing correctly.
Check adjustment ac-
cording to pos. d) below.
d)
Too high temperature at high load
1 Cooling is insufficient.
Check the temperature after the
central cooler. Check that the valve is fully open. Utilize the
indicator pin (18).
2 Defective low temperature element.
Change the ele-
ment.
3 Check that the piston
(3) is in low temperature position,
utilize the position of the screw (2).
4 If the position piston
(3) is in wrong position, check pres-
sure (14) before the cylinder.
5 If there is no pressure,
the valve is jamming. Open and
clean the valve.
6 If there is pressure,
the position control system is faulty.
7 If the pressure disappears
when opening the connection
(14) the drain hole of the three-way valve (2), Fig 19-5, can be
clogged. Clean the drain opening.
8 If the air flow does not stop,
check the switch (3), Fig 19-
5.
9 If the switch is intact,
clean the three-way valve (2), Fig
19-5, or change if damaged.
19.4.2.3 Adjustment of the valve
For correct closing position, adjust as follows:
1 The air supply to the valve
should be shut off and drained
before adjusting the valve.
2 The temperatures of the valves
must not exceed 25°C
when adjusting. This is to guarantee that the low temperature
elements are completely compressed.
3 Remove the screw (11).
4 Turn the adjusting nut (1) clockwise
until the indication
pin (18) starts moving. Then turn the adjusting nut counter
clockwise about one turn.
5 Mount the screw (11)
in the nearest hole to lock the ad-
justment.
22-9601
Cooling Water System
19
VASA 22
19 - 13
Summary of Contents for Vasa R22
Page 14: ...Appendix B Welding Precautions 200147 00 4...
Page 42: ...02 Fuel Lubricating Oil Cooling Water 22 9601 02 22 VASA 22...
Page 60: ...03 Start Stop and Operation 22 9632 03 12 VASA 22...
Page 72: ...04 Maintenance Schedule 22 9845 III 04 12 MD HF...
Page 92: ...06 II Adjustments Clearances and Wear limits 22 9601 06 6 VASA 22...
Page 116: ...08 Operating Troubles Emergency Operation 22 9601 08 8 VASA 22...
Page 144: ...11 Crank Mechanism 22 9601 11 18 VASA 22...
Page 156: ...12 Cylinder Head with Valves 22 9601 12 12 VASA 22...
Page 164: ...13 Camshaft Driving Gear 22 9601 13 8 VASA 22...
Page 172: ...14 Valve Mechanism and Camshaft 22 9601 14 8 VASA 22...
Page 183: ...22 200520 Turbocharging and Air Cooling 15 VTR Turbocharger 15 11...
Page 189: ...15 III Turbocharging and Air Cooling 22 8604 15 6 VTR 161 251 Turbochargers...
Page 209: ...17 Fuel system 22 9601 17 8 VASA 22...
Page 229: ...18 Lubricating Oil System 22 9601 18 20 VASA 22...
Page 247: ...19 Cooling Water System 22 9601 19 18 VASA 22...
Page 261: ...21 Starting Air System 22 9601 21 10 VASA 22...