ALPHA/DELTA INSTALLATION & MAINTENANCE CHECKLIST
ALPHA/DELTA INSTALLATION AND MAINTENANCE
CHECKLIST
Checked
Good
Needs
Attention
N/A
16�
Loop Detector - Test
Verify that the ground loops have been occupied
and the gate responds correctly. Test the loop
occupation with the type of vehicles that will be
using the gate. The loop detector sensitivity should
be set as high as possible without false detections.
Ensure loop phasing is correct.
17�
Loop Inspection
Ensure all of the ground loop path is covered with
sealant. Exposed areas should be resealed.
18�
Accessory Device Programming
Program changes through the Kinetic Installer
Menu for the accessory devices, installed as
appropriate for site requirements.
19�
Close Timer
Set the close timer if required and record the
setting:
Default is 0.
20�
IES Sensitivity
Test IES sensitivity and adjust if needed. Record
setting:
Default is 2.
21�
Usage Class
Record Usage Class setting in Initial Setup menu:
22�
Gate Speed
Record the Open Speed settings:
Record the Close Speed settings: