Alpha/Delta (Kinetic Operator) Installation and Maintenance Manual
Revision 1 - MAY 2023
109
INSTALLER MENU FUNCTIONS
Table 6. SmartDC Controller - Installer Menu Functions
Ref.
No�
Installer Menu
Setting Options
(
Bold
= Factory Settings)
Menu Tasks and Explanations
Associated
DC Controller
Connections
Display
14
FO 0 (OFF)
FIRE DEPT OPEN
0 = disabled
1 = enabled
Enables Fire Department Open input.
When set to 1, the open signal received
by the operator overrides all photoelectric
eyes and edge sensors and opens the gate.
Pressing the RESET button (or the OPEN
push-button) is required before the gate
can be closed.
+24V DC
EMERG OPEN
15
SE 2
IES SENSITIVITY
0 = maximum sensitivity
2 = default setting
9 = least sensitivity
Adjusts sensitivity of the internal inherent
entrapment sensor (IES). Available settings
are 0 to 9 with 9 being the least sensitive.
Wallace Perimeter Security strongly
recommends that you avoid setting the IES
sensitivity higher than 6.
Note: Before changing IES sensitivity,
make sure that the gate rolls smoothly
without obstruction. Fix any issues with
gate hardware.
See Note.
16
SS 0 (OFF)
IES STOP ONLY
0 = stop, reverse for 2s
1 = stop only
In a Usage Class 4 environment, the
operator can be set to stop the gate and
not reverse gate travel after an IES trip.
Note: This menu option only appears
when the Usage Class is set to 4.
(N/A)
17
LC 0 (0.0 SECS)
LEAF DELAY CLOSE
0 = no delay
1 through 20 in ½ second
increments
For example:
1 = ½ second
10 = 5 seconds
20 = 10 seconds
Only appears if the gate operator is set
up as a Primary or a Secondary. Available
settings are 1 through 20. Each increment
adds ½ second time delay following a
command to close before the operator
activates. Provides up to a 10 second time
delay.
DUAL GATE
inputs on both
operators.
18
LO 0 (0.0 SECS)
LEAF DELAY OPEN
0 = no delay
1 through 20 in ½ second
increments
For example:
1 = ½ second
10 = 5 seconds
20 = 10 seconds
Only appears if the gate operator is set
up as a Primary or a Secondary. Available
settings are 1 through 20. Each increment
adds ½ second time delay following a
command to open before the operator
activates. Provides up to a 10 second time
delay.
DUAL GATE
inputs on both
operators.