WIRING 230VAC POWER
Do not connect the 115VAC service
outlet to 230VAC power supply wires.
To use the service outlet with 230VAC
supply power, a separate neutral wire
(white) must be run from the power
source. Follow guidelines according
to National Electrical Code Article 250.
To connect to 230VAC power, take the following steps:
1�
Make sure the AC power is turned off at its source and the DC and AC power switches on the operator
are in the OFF position.
2�
Remove the High Voltage Protection cover by unscrewing the two Phillips-head screws that secure
it. See
“Figure 16. Wiring AC Power” on page 70
�
3�
Toggle the voltage selector switch from 115V to 230V. See Figure 17. Replace the cover and secure
it�
4�
Access the input power wires by removing the two Phillips-head screws that secure the Junction Box
Cover. See
“Figure 16. Wiring AC Power” on page 70
�
5�
Wire nut or crimp bond the power supply wires to the black and white lead wires coming from the
AC power switch (no label).
6�
Wire nut or crimp bond the equipment ground wire to the green ground wire in the junction box.
7�
Neatly organize all wire connections and secure the junction box cover with the two Phillips-head
screws.
8�
Place the 230V 1Ø label on the Junction Box Cover over the 115V 1Ø label.
Figure 17. Voltage Selector Switch Set to 230V