362 I/O Modules
WAGO-I/O-SYSTEM 750
750-882 Media Redundancy ETHERNET Controller
Manual
1.5.0
13.2.5.13 LON
®
FTT Module
753-648
The process image of the LON
®
FTT module consists of a control/status byte and
23 bytes of bidirectional communication data that is processed by the WAGO-I/O-
PRO
function block "LON_01.lib". This function block is essential for the function
of the LON
®
FTT module and provides a user interface on the control side.
13.2.5.14 EnOcean Radio Receiver
750-642
The EnOcean radio receiver has a total of 4 bytes of user data in both the Input
and Output Process Image (3 bytes of module data and 1 byte of control/status).
The following tables illustrate the Input and Output Process Image, which have 2
words mapped into each image. Word alignment is applied.
Table 411: EnOcean Radio Receiver 750-642
Input Process Image
Offset
Byte Destination
Description
High Byte
Low Byte
0
D0
S
Data byte
Status byte
1
D2
D1
Data bytes
Output Process Image
Offset
Byte Destination
Description
High Byte
Low Byte
0
-
C
not used
Control byte
1
-
-
not used
13.2.5.15 MP Bus Master Module
750-643
The MP Bus Master Module has a total of 8 bytes of user data in both the Input
and Output Process Image (6 bytes of module data and 2 bytes of control/status).
The following table illustrates the Input and Output Process Image, which have 4
words mapped into each image. Word alignment is applied.
Table 412: MP Bus Master Module 750-643
Input and Output Process Image
Offset
Byte Destination
Description
High Byte
Low Byte
0
C1/S1
C0/S0
extended Control/
Status byte
Control/status
byte
1
D1
D0
Data bytes
2
D3
D2
3
D5
D4