186 Configuring via the Web-Based Management System (WBM) WAGO-I/O-SYSTEM 750
750-882 Media Redundancy ETHERNET Controller
Manual
1.5.0
Table: WBM Page “PLC”
PLC Features
Function
Default
Description
I/O
configu-
ration
Compatible
handling for
ea-config.xml
Activate, if the write authorizations must be assigned to
the outputs of all bus terminals based on an existing
file “ea-config.xml”.
Here, note whether a control system configuration has
already been created and, if so, whether this
configuration is correct or incorrect (see the following
table).
The current process values are displayed on the
website “IO config”, in addition to the displayed data
channels.
Disable, if the write authorizations must be assigned to
the outputs of all bus terminals of the PLC
Here, note whether a control system configuration has
already been created and, if so, whether this
configuration is correct or incorrect (see the following
table).
I/O configuration
(function activated)
I/O configuration
(function deactivated,
standard setting):
No control system
configuration has
been created in the
project
Writing privileges to the
outputs of
all modules are
assigned on the
basis of an existing ea-
config.xml.
The ea-config.xml file
must be
completely error-free;
otherwise the
writing privileges for all
modules
will be assigned to the
standard
fieldbus.
The outputs for all
modules are
assigned to the PLC.
Any ea-config.xml file
that may already be
present is ignored and
overwritten.
Correct control
system configuration
has been created in
the project
Writing privileges to the module outputs is taken
from the control system
configuration. A corresponding ea-config.xml file is
generated in the file
system.
Incorrect control
system configuration
has been created in
the project
The standard fieldbus is granted writing privileges
to the outputs of all the
modules.
Insert
monitoring
entries into
ea-config.xml
Activate to also display the current process values on
the WBM page “IO config” for the displayed data
channels.
Disable, if no process values must be displayed on the
WBM page “IO config”.