280 Fieldbus Communication
WAGO-I/O-SYSTEM 750
750-882 Media Redundancy ETHERNET Controller
Manual
1.5.0
Instance 1
Table 214: Port class (F4
hex
) – Instance 1 for ETHERNET Port X1
Attribute ID Acces
s
NV Name
Data type Description
Default value
1
Get
V
Port Type
UINT
-
4 (0x0004)
2
Get
V
Port Number UINT
CIP port number
2 (0x0002)
(EtherNet/IP)
3
Get
V
Port Object
UINT
Number of 16 bit
words in the
following path
2 (0x0002)
Padded
EPATH
Object, which
manages this port
0x20 0xF5
0x24 0x01
(equals TCP/IP
Interface Object)
4
Get
V
Port Name
SHORT_
STRING
Port name
“”
7
Get
V
Node Address Padded
EPATH
Port segment (IP
address)
IP address port 1
Instance 2
Table 215: Port class (F4
hex
) – Instance 2 for ETHERNET Port X2
Attribute ID Acces
s
NV Name
Data type Description
Default value
1
Get
V
Port Type
UINT
-
4 (0x0004)
2
Get
V
Port Number UINT
CIP port number
3 (0x0003)
(EtherNet/IP)
3
Get
V
Port Object
UINT
Number of 16 bit
words in the
following path
2 (0x0002)
Padded
EPATH
Object, which
manages this port
0x20 0xF5
0x24 0x02
(equals TCP/IP
Interface Object)
4
Get
V
Port Name
SHORT_
STRING
Port name
“”
7
Get
V
Node Address Padded
EPATH
Port segment (IP
address)
IP address port 2
Common Services
Table 216: Port class (F4
hex
) – Common service
Service code Service
available
Service-Name
Description
Class Instance
01
hex
Yes
Yes
Get_Attribute_All
Supplies contents of all attributes
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate attribute