222 Fieldbus Communication
WAGO-I/O-SYSTEM 750
750-882 Media Redundancy ETHERNET Controller
Manual
1.5.0
12.1.2.7.2 Traps
Standard Traps
For specific events, the SNMP agent will independently send one of the following
messages without polling the manager.
Enable event messages (traps) in the WBM!
Initially enable the event messages in the WBM in menu “SNMP” under “Trap
Enable”. Traps in version 1, 2c and 3 may be activated separately.
The following messages are triggered automatically as traps (SNMPv1) by the
fieldbus coupler/controller:
Table 84: Standard Traps
TrapType/TrapNumber/OI
D of the provided value
Name
Event
TrapType = 0
ColdStart
Restart the coupler/controller
TrapType = 1
WarmStart
Reset via service switch
TrapType = 3
EthernetUp
Network connection detected
TrapType = 4
AuthenticationFailure Unauthorized (abortive) MIB
access
TrapType = 6/
ab Trap-Nummer 25
benutzerspezifisch
enterpriseSpecific
Enterprise-specific messages and
function poll in the PFC program
starting with enterprise trap number 25