WAGO-I/O-SYSTEM 750
Fieldbus Communication 279
750-882 Media Redundancy ETHERNET Controller
Manual
1.5.0
12.3.5.8 Connection Manager (06
hex
)
The “Connection Manager Object” provides the internal resources that are
required for the input and output data and explicit messages. In addition, the
administration of this resource is an assignment of the “Connection Manager
Object”.
For each connection (input and output data or explicit), another instance of the
connection class is created. The connection parameters are extracted from the
“Forward Open” service, which is responsible for establishing a connection.
The following services are supported for the first instance:
•
Forward_Open
•
Unconnected_Send
•
Forward_Close
No class and instance attributes are visible.
12.3.5.9 Port Class (F4
hex
)
The “Port Class Object” specifies the existing CIP ports on the fieldbus controller.
There is one instance for each CIP port.
Instance 0 (Class Attributes)
Table 213: Port class (F4
hex
) – Class
Attribute ID Acces
s
Name
Data type Description
Default value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
2 (0x0002)
3
Get
Num Instances UINT
Number of current ports
1 (0x0001),
2 (0x0002)
8
Get
Entry Port
UINT
Instance of the port object
where the request arrived.
1 (0x0001)
9
Get
All Ports
Array of
Struct
UINT
Array with instance attributes
1 and 2 of all instances
0 (0x0000)
0 (0x0000)
4 (0x0004)
2 (0x0002)
4 (0x0004)
2 (0x0002)