WAGO-I/O-SYSTEM 750
Fieldbus Communication 283
750-882 Media Redundancy ETHERNET Controller
Manual
1.5.0
Instance 2
Table 219: TCP/IP interface (F5
hex
) – Instance 2 for ETHERNET Port X2
Attribute ID Acces
s
NV Name
Data type Description
Default
value
1
Get
V
Status
DWORD
Interface state
-
2
Get
V
Configuration
Capability
DWORD
Interface flags for possible
kinds of configuration
0x00000017
3
Set
NV Configuration
Control
DWORD
Specifies, how the device gets
is TCP/IP configuration after
the first Power On
0x00000011
4
Get
V
Physical Link
Object
STRUCT
of
Path size
UINT
Number of 16 Bit words in the
following path
0x0002
Path
Padded
EPATH
Logical path, which points to
the physical Link object
0x20 0xF6
0x24 0x02
(equates to
the Ethernet
Link Object)
5
Set
NV Interface
Configuration
STRUCT
of
-
IP Address
UDINT
IP address
0
Network Mask UDINT
Network mask
0
Gateway
Address
UDINT
IP address of default gateway 0
Name Server UDINT
IP address of the primary
name of the server
0
Name Server
2
UDINT
IP address of the secondary
name of the server
0
Domain Name STRING
Default domain name
“”
6
Set
NV Host Name
STRING
Device name
“”
Common Services
Table 220: TCP/IP interface (F5
hex
) – Common service
Service code Service
available
Service name
Description
Class Instance
01
hex
Yes
Yes
Get_Attribute_All
Supplies contents of all attributes
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate attribute
10
hex
No
Yes
Set_Attribute_Single Modifies an attribute value