WAGO-I/O-SYSTEM 750
Fieldbus Communication 297
750-882 Media Redundancy ETHERNET Controller
Manual
1.5.0
12.3.5.19 Discrete Output Point Extended 2 (6E
hex
)
The extension of the “Discrete Output Point” class enables the exchange of data
from a fieldbus node that contains over 510 digital output points (DOPs). This
instance cope of the “Discrete Output Point Extended 1” class covers the DOPs
from 511 to 765 in the fieldbus node.
Instance 0 (Class Attributes)
Table 247: Discrete Output Point Extended 2 (6E
hex
) – Class
Attribute ID Access Name
Data type Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
-
Instance 511 ... 765 (Digital output value 511 up to 765)
Table 248: Discrete Output Point Extended 2 (6E
hex
) – Instance 511...765
Attribute ID Access Name
Data type Description
Default
value
1
Get
DopObj_Value BYTE
Digital Output
(only Bit 0 valid)
-
Common Services
Table 249: Discrete Output Point Extended 2 (6E
hex
) – Common service
Service
code
Service available
Service-Name
Description
Class Instance
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate
attribute
10
hex
No
Yes
Set_Attribute_Single Modifies an attribute value
12.3.5.20 Discrete Output Point Extended 3 (72
hex
)
The extension of the “Discrete Output Point” class enables the exchange of data
from a fieldbus node that contains over 765 digital output points (DOPs). The
instance scope of the “Discrete Output Point Extended 2” class covers DOPs
from 766 to 1020 in the fieldbus node.
Instance 0 (Class Attributes)
Table 250: Discrete Output Point Extended 3 (72
hex
) – Class
Attribute ID Access Name
Data type Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
-