WAGO-I/O-SYSTEM 750
Fieldbus Communication 289
750-882 Media Redundancy ETHERNET Controller
Manual
1.5.0
Instance 3 – Internal Port 3
Table 224: Ethernet link (F6
hex
) – Instance 3
Attribute ID Acces
s
Name
Data type
Description
Default value
1
Get
Interface Speed UDINT
Transfer rate
100 (0x64)
2
Get
Interface Flags
DWORD
Interface
configuration and
status information
3 (0x03) – Link
active (Bit 0),
Full duplex (Bit 1)
3
Get
Physical Address
ARRAY of 6
UINTs
MAC layer address
MAC ID of the
device
6
Set
Interface Control STRUCT of:
Configuration of the
physical interface
-
Control Bits
WORD
Interface
configuration bits
3 (0x03) – Link
active (Bit 0),
Full duplex (Bit 1)
Forced Interface
Speed
UINT
Baud rate
100 (0x64)
7
Get
Interface Type
UINT
Interface type
1 (0x01) – internal
Port
8
Get
Interface Status
UINT
Interface status
1 (0x01) – active
9
Get
Admin Status
UINT
Admin status
1 (0x01) – active
10
Get
Interface Label
SHORT_
STRING
Name of the interface “Internal Port 3”
Common Services
Table 225: Ethernet link (F6
hex
) – Common service
Service code Service
available
Service-Name
Description
Class Instance
01
hex
Yes
Yes
Get_Attribute_All
Supplies contents of all attributes
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate attribute
10
hex
No
Yes
Set_Attribute_Single Modifies an attribute value
Changes with service “Set_Attribute_Single” not directly effective!
Attributes (particularly the attributes 6 and 9) which were changed over the
service “Set_Attribute_Single”, become only effective after the next Power-On-
Reset of the controller.