WAGO-I/O-SYSTEM 750
Fieldbus Communication 301
750-882 Media Redundancy ETHERNET Controller
Manual
1.5.0
Common Services
Table 264: Analog Input Point Extended 3 (73
hex
) – Common service
Service
code
Service available
Service name
Description
Class Instance
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate
attribute
12.3.5.25 Analog Output Point (68
hex
)
This class enables the reading of data of a particular analog output point (AOP).
An analog output point is part of an analog output module.
Instance 0 (Class Attributes)
Table 265: Analog Output Point (68
hex
) – Class
Attribute ID Access Name
Data type Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2
Get
Max Instance
UINT
Max. number of instances
-
Instance 1 ... 255 (Analog output value 1 up to 255)
Table 266: Analog Output Point (68
hex
) – Instance 1...255
Attribute ID Access Name
Data type Description
Default
value
1
Get
AopObj_Value ARRAY of
BYTE
Analog Output
-
2
Get
AopObj_Value_
Length
USINT
Length of the output data
AopObj_Value (in byte)
-
Common Services
Table 267: Analog Output Point (68
hex
) – Common service
Service
code
Service available
Service name
Description
Class Instance
0E
hex
Yes
Yes
Get_Attribute_Single Supplies contents of the appropriate
attribute
10
hex
No
Yes
Set_Attribute_Single Modifies an attribute value