70 Process Image
WAGO I/O System 750 XTR
750-495/040-010 3-Phase POM 20KV 300A XTR
Manual
Version 1.0.0
Calculation of the Current-Dependent Measured Values (Current, Power and
Energy)
Overvoltage Threshold L1
Process value
0x002DC6C0 (3,000,000)
PI Scaling Factor
0.0001 A
Formula
Measured value = process value × PI scaling
factor
Measured value for current 300 A
Active Power
Process value
0x14A5CC10 (346,410,000)
PI Scaling Factor
0.01 W
Formula
Measured value = process value × PI scaling
factor
Measured value for power
3,464,100 W
Active Energy
Register 35*
6
Process value
0x00008751 (34,641)
PI Scaling Factor
0.1 Wh
Formula
Measured value = process value × PI scaling
factor
Measured value for energy 3,464.1 kWh
*
Register 35: The setting in the register defines the PI scaling factor for energy values
Pos: 65 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1