WAGO I/O System 750 XTR
Appendix 123
750-495/040-010 3-Phase POM 20KV 300A XTR
Manual
Version 1.0.0
Table 66: Parameters 30 and 31
Parameters 30 and 31 – Overcurrent Threshold Value, Phase 3
Function
Data Type Access
Factory Setting
Overcurrent threshold value, phase 3
Resolution: 0.1 mA
UINT
R/W
0x02FAF080
(5000 A)
0:
The overvoltage threshold check is disabled
≥ 1
:
Value of the overvoltage threshold
Table 67: Parameter 34
Parameter 34 – Observation Interval, Arithmetic Mean Value, Phase 1
Function
Data Type Access
Factory Setting
Observation interval, arithm. mean value, phase
1
UINT
R/W
0x0004
0:
The arithmetic mean is calculated over 5 seconds
1:
The arithmetic mean is calculated over 10 seconds
2:
The arithmetic mean is calculated over 15 seconds
3:
The arithmetic mean is calculated over 30 seconds
4:
The arithmetic mean is calculated over 60 seconds
5:
The arithmetic mean is calculated over 300 seconds
6:
The arithmetic mean is calculated over 480 seconds
7:
The arithmetic mean is calculated over 600 seconds
8:
The arithmetic mean is calculated over 900 seconds
≥ 9:
-reserved-
Table 68: Parameter 35
Parameter 35 – Observation Interval, Arithmetic Mean Value, Phase 2
Function
Data Type Access
Factory Setting
Observation interval, arithm. Mean value, phase
2
UINT
R/W
0x0004
0:
The arithmetic mean is calculated over 5 seconds
1:
The arithmetic mean is calculated over 10 seconds
2:
The arithmetic mean is calculated over 15 seconds
3:
The arithmetic mean is calculated over 30 seconds
4:
The arithmetic mean is calculated over 60 seconds
5:
The arithmetic mean is calculated over 300 seconds
6:
The arithmetic mean is calculated over 480 seconds
7:
The arithmetic mean is calculated over 600 seconds
8:
The arithmetic mean is calculated over 900 seconds
≥ 9:
-reserved-