WAGO I/O System 750 XTR
Commissioning 91
750-495/040-010 3-Phase POM 20KV 300A XTR
Manual
Version 1.0.0
8.2.2
Tabs “Phase L1,” “Phase L2” and “Phase L3”
Use the "Phase L1," "Phase L2" and "Phase L3" tabs to configure
minimum/maximum values and general parameters. These settings are saved to
the I/O module.
Click the “Save” button to apply the value settings.
•
For “Min./Max. Values,” enter the undervoltage limit, the overvoltage
threshold and the undercurrent threshold. If this value is not reached or is
exceeded, an error bit is set in the status byte of the process image and a
red error LED is enabled.
Also specify whether or not the measured min./max values for current,
voltage, power and frequency should be reset automatically after a certain
amount of time. If they should, specify the reset interval.
•
You can also make 2 general settings: the interval setting for the calculation
of the arithmetic mean (in s) and the interval setting for peak value
measurement (in half-waves).
Figure 22: “Phase L1” Tab