122 Appendix
WAGO I/O System 750 XTR
750-495/040-010 3-Phase POM 20KV 300A XTR
Manual
Version 1.0.0
Table 60: Parameter 22
Parameter 22 – Storage Interval, Energy Consumption
Function
Data Type Access
Factory Setting
- Corresponds to register 46 (see section “Register Assignment”)
Table 61: Parameter 23
Parameter 23 – Overvoltage Threshold Value, Phase 1
Function
Data Type
Access
Factory Setting
Overvoltage threshold, phase 1,
Resolution: 1 V
UINT
R/W
0x5208
(21,000 V)
0:
The overvoltage threshold check is disabled
≥ 1
:
Value of the overvoltage threshold
Table 62: Parameter 24
Parameter 24 – Overvoltage Threshold Value, Phase 2
Function
Data Type
Access
Factory Setting
Overvoltage threshold, phase 2,
Resolution: 1 V
UINT
R/W
0x5208
(21,000 V)
0:
The overvoltage threshold check is disabled
≥ 1
:
Value of the overvoltage threshold
Table 63: Parameter 25
Parameter 25 – Overvoltage Threshold Value, Phase 3
Function
Data Type
Access
Factory Setting
Overvoltage threshold, phase 3,
Resolution: 1 V
UINT
R/W
0x5208
(21,000 V)
0:
The overvoltage threshold check is disabled
≥ 1
:
Value of the overvoltage threshold
Table 64: Parameters 26 and 27
Parameters 26 and 27 – Overcurrent Threshold Value, Phase 1
Function
Data Type
Access
Factory Setting
Overcurrent threshold value, phase 1
Resolution: 0.1 mA
UINT
R/W
0x02FAF080
(5000 A)
0:
The overvoltage threshold check is disabled
≥ 1
:
Value of the overvoltage threshold
Table 65: Parameters 28 and 29
Parameters 28 and 29 – Overcurrent Threshold Value, Phase 2
Function
Data Type
Access
Factory Setting
Overcurrent threshold value, phase 2
Resolution: 0.1 mA
UINT
R/W
0x02FAF080
(5000 A)
0:
The overvoltage threshold check is disabled
≥ 1
:
Value of the overvoltage threshold