120 Appendix
WAGO I/O System 750 XTR
750-495/040-010 3-Phase POM 20KV 300A XTR
Manual
Version 1.0.0
Table 51: Register 62
Register 62 –
Power-On Self-Test
Function
Data Type Access
Factory Setting
Power-On Self-Test
UINT
R
None
Bit 0: -reserved-
Bit 1: FLASH checksum error
0:
No FLASH checksum error was detected
1:
A FLASH checksum error was detected
Bit 2 ... 6: -Reserved-
Bit 7: self test running
0:
No self test is currently running
1:
A self test is currently running
Bit 8: main image of the calibration data
0:
The main image of the calibration data is OK
1:
The main image of the calibration data was restored (CRC16 error)
Bit 9: energy meter
0:
The energy meter is OK
1:
The energy meter was restored (CRC16 error)
Bit 10: IOM executability
0:
IOM is executable
1:
IOM is not executable due to the lack of a valid hardware encoding
Bit 11: calibration data set
0:
A valid calibration data set exists.
1:
A valid calibration data set no longer exists.
Bit 12: inter-processor interface (SPI)
0:
No error occurred
1:
An error has occurred
Bit 13: reset during ongoing operation
0:
The AFE chip did not perform a reset during ongoing operation
1:
The AFE chip performed a reset during ongoing operation
Bit 14: -reserved-
Bit 15: -reserved-