124  Appendix 

WAGO I/O System 750 XTR 

 

 

750-495/040-010 3-Phase POM 20KV 300A XTR 

Manual 

 

Version 1.0.0  

 

Table 69: Parameter 36

 

Parameter 36 – Observation Interval, Arithmetic Mean Value, Phase 3 

Function 

Data Type  Access 

Factory Setting 

Observation interval, arithm. Mean value, phase 

UINT 

R/W 

0x0004 

0: 

The arithmetic mean is calculated over 5 seconds 

1: 

The arithmetic mean is calculated over 10 seconds 

2: 

The arithmetic mean is calculated over 15 seconds 

3: 

The arithmetic mean is calculated over 30 seconds 

4: 

The arithmetic mean is calculated over 60 seconds 

5: 

The arithmetic mean is calculated over 300 seconds 

6: 

The arithmetic mean is calculated over 480 seconds 

7: 

The arithmetic mean is calculated over 600 seconds 

8: 

The arithmetic mean is calculated over 900 seconds 

≥ 9:

 

-reserved- 

 

Table 70: Parameter 37

 

Parameter 37 – Interval, Autom. Reset Min/Max Values, Phase 1 

Function 

Data Type  Access 

Factory Setting 

Time constant for automatic deletion of minimum 

and maximum values of phase 1, resolution 200 

ms,  

activation via register 32, bit 8 required 

UINT 

R/W 

0x000A (2 s) 

 

Table 71: Parameter 38

 

Parameter 38 – Interval, Autom. Reset Min/Max Values, Phase 2 

Function 

Data Type  Access 

Factory Setting 

Time constant for automatic deletion of minimum 

and maximum values of phase 2, resolution 200 

ms,  

activation via register 32, bit 9 required 

UINT 

R/W 

0x000A (2 s) 

 

Table 72: Parameter 39

 

Parameter 39 – Interval, Autom. Reset Min/Max Values, Phase 3 

Function 

Data Type  Access 

Factory Setting 

Time constant for automatic deletion of minimum 

and maximum values of phase 3, resolution 200 

ms,  

activation via register 32, bit 10 required 

UINT 

R/W 

0x000A (2 s) 

 

Summary of Contents for I/O System 750 XTR 750-495/040-010

Page 1: ...0 010 3 Phase POM 20KV 300A XTR 3 Phase Power Measurement 20 kV AC 300 A Extreme only in connection with sensors according to section Measurement of Voltage Current and Power Version 1 0 0 Pos 3 Alle...

Page 2: ...ort wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can never be fully excluded we always appreciate any information o...

Page 3: ...1 Disposal 11 2 1 4 1 1 Electrical and Electronic Equipment 11 2 1 4 1 2 Packaging 12 2 2 Safety Advice Precautions 13 3 Device Description 16 3 1 View 18 3 2 Connectors 19 3 2 1 Data Contacts Local B...

Page 4: ...ting 71 6 1 Mounting Sequence 72 6 2 Inserting and Removing Devices 73 6 2 1 Inserting the I O Module 73 6 2 2 Removing the I O Module 74 7 Connect Devices 75 7 1 Protection against Hazardous Touch Vo...

Page 5: ...ng View 103 8 2 5 7 Information View 104 9 Firmware Update 105 10 Appendix 106 10 1 Examples of CSV Files 106 10 1 1 Snapshot 106 10 1 2 Measurement Recording 111 10 2 Factory Settings 112 10 3 Regist...

Page 6: ...eich G ltigkeitsbereich Dokumentation I O Modul 750 xxxx ohne Variantenangabe 14 mod_1358944037947_21 docx 109346 1 This documentation is only applicable to the I O module 750 495 040 010 3 Phase POM...

Page 7: ...ine Module berschriften Ebene 2 Urheberschutz berschrift 2 23 mod_1435647042188_21 docx 184808 2 1 1 3 Copyright Pos 15 2 Alle Serien Allgemeine Module Rechtliches Allgemeines Urheberschutz ausf hrlic...

Page 8: ...5 4 Alle Serien Allgemeine Module Sicherheits und sonstige Hinweise Vorsicht Vorsicht _Warnung vor Personensch den allgemein_ Erl uterung 13 mod_1343310028762_21 docx 101038 1 Personal Injury Indicate...

Page 9: ...Module berschriften Ebene 2 Schriftkonventionen berschrift 2 23 mod_1435647186005_21 docx 184814 2 1 1 6 Font Conventions Pos 15 10 Alle Serien Allgemeine Module Rechtliches Allgemeines Schriftkonvent...

Page 10: ...tions All sequences implemented on WAGO I O System 750 devices may only be carried out by electrical specialists with sufficient knowledge The specialists must be familiar with the current norms and g...

Page 11: ...o parts that can be serviced or repaired by the user The following actions will result in the exclusion of liability on the part of WAGO Kontakttechnik GmbH Co KG Repairs Changes to the hardware or so...

Page 12: ...Z 28 mod_1485262995837_0 docx 404006 1 Pos 18 9 4 Alle Serien Allgemeine Module berschriften Ebene 5 Verpackung berschrift 5 32 mod_1537447044202_21 docx 501662 5 1 2 1 4 1 2 Packaging Pos 18 9 5 Alle...

Page 13: ...9 8 and do so in accordance with the information in the section Technical Data Pos 18 15 Serie 750 WAGO I O SYSTEM Wichtige Erl uterungen alte Struktur Sicherheits und sonstige Hinweise Gefahr Gefahr...

Page 14: ..._1567504456177_21 docx 558298 1 Only connect or disconnect lines when power is safely isolated Hazardous voltages and currents are present on the primary side of the sensors used Contact with the line...

Page 15: ...housing and soiled contacts with propanol Pos 18 19 5 Alle Serien Allgemeine Module Sicherheits und sonstige Hinweise Achtung Achtung Kein Kontaktspray verwenden 6 mod_1260181290808_21 docx 46755 1 Do...

Page 16: ...a 4 quadrant display as has been implemented in the display of the measured values in WAGO I O CHECK among other things The measured values provided are described in the following sections The voltage...

Page 17: ...is possible when groups of modules are electrically isolated on the field side i e electrically isolated power supply Pos 24 Serie 750 WAGO I O SYSTEM Ger tebeschreibung alte Struktur Einleitung Eins...

Page 18: ...495 040 010 Pos 28 Serie 750 WAGO I O SYSTEM Ger tebeschreibung alte Struktur Ansicht Ansicht CageClamp _Legende mit LEDs_ohne Leistungskontakte 16 mod_1371816091053_21 docx 124052 1 Table 4 Legend f...

Page 19: ...spring contacts in order to avoid soiling or scratching Pos 32 3 Serie 750 WAGO I O SYSTEM Wichtige Erl uterungen alte Struktur Sicherheits und sonstige Hinweise Achtung Achtung ESD Auf Potentialausgl...

Page 20: ...sors to be connected each with a two wire connection see also section Connecting Devices All N connections are connected internally to each other and are used for the reference potential N Therefore a...

Page 21: ...bus communication Green Operational readiness and uninterrupted local bus communication Note If the watchdog has been deactivated the LED remains lit see section Commissioning Parameterization with W...

Page 22: ...63 1 The I O module 750 495 040 010 has no operating elements Pos 45 Alle Serien Allgemeine Module berschriften Ebene 2 Schematisches Schaltbild berschrift 2 4 mod_1240984441312_21 docx 31967 2 1 3 5...

Page 23: ...f Contents 23 750 495 040 010 3 Phase POM 20KV 300A XTR Manual Version 1 0 0 Figure 6 Schematic Circuit Diagram for 750 495 040 010 Pos 47 Dokumentation allgemein Gliederungselemente Seitenwechsel 3 m...

Page 24: ...m upper edge of DIN rail 60 6 mm Depth 100 mm Weight 92 g Degree of protection IP20 Pos 49 2 Serie 750 WAGO I O SYSTEM Ger tebeschreibung alte Struktur Technische Daten AI Technische Daten 750 0495 04...

Page 25: ...l voltage UN 225 mV Upper measurement range 540 75 mV Input resistance 20 8 k 1 Permitted signal voltage 90 V max continuous 1 Frequency range Mains frequency 45 Hz 65 Hz Harmonic analysis 45 2665 Hz...

Page 26: ...lues Line to line voltage power output energy power factors line frequency harmonic analysis up to the 41st harmonic Process data update Voltage Lx N 40 ms Voltage min max Lx N 40 ms 2 Voltage Lx Ly 3...

Page 27: ...oltages and currents 3 620 ms at 100 1300 ms after power on Active power and apparent power 2 415 ms at 60 915 ms at 100 Reactive power 2 715 ms at 60 1215 ms at 100 Harmonic Analysis 790 ms Do not al...

Page 28: ...pper range value Pos 49 3 Serie 750 WAGO I O SYSTEM Ger tebeschreibung alte Struktur Technische Daten VS Variablensteuerung Technische Daten Kommunikation VS 4 mod_1242119312796_21 docx 32970 3 1 3 6...

Page 29: ...ions Table 18 Technical Data Climatic Environmental Conditions Surrounding air temperature operation 40 C 70 C Surrounding air temperature storage 40 C 85 C Relative humidity 95 Elevation above sea le...

Page 30: ...listed in the document Overview on WAGO I O SYSTEM 750 approvals which you can find via the internet under www wago com DOWNLOADS Documentation System Description Pos 52 2 Serie 750 WAGO I O SYSTEM G...

Page 31: ...docx 56645 1 750 495 040 010 I O modules meet the following standards and guidelines Pos 56 2 Serie 750 WAGO I O SYSTEM Ger tebeschreibung alte Struktur Normen und Richtlinien Normen und Richtlinien X...

Page 32: ...0 4 3 EN 60255 26 IEEE C37 90 2 20 V m 80 MHz 1 GHz 10 V m 1 GHz 3 GHz Fast Electrical Transient Disturbances Burst EN 61000 4 4 EN 60255 26 IEEE C37 90 1 4 kV Surge Voltage Surge EN 61000 4 5 EN 6025...

Page 33: ...conductor 2 5 kV conductor ground Voltage Dips Short term Interruptions and Voltage Fluctuations to DC Supply Inputs EN 61000 4 29 EN 60255 26 Standard not applicable Harmonics Shipbuilding Max 2 W DC...

Page 34: ...z 3 GHz 56 dB V m AV 1 GHz 3 GHz 80 dB V m Peak 3 GHz 6 GHz 60 dB V m AV 3 GHz 6 GHz Conducted Emission of Interference Line Connection AC Voltage EN 61000 6 3 EN 55032 Class B Standard not applicable...

Page 35: ...onents up to a frequency of 2 kHz with 65 Hz line frequency The connection for each of the voltage and current sensors for the 3 phases to the measurement channels is a 2 wire connection Low pass filt...

Page 36: ...c analysis for one selected phase Lsel L1 L2 or L3 RMS current fundamental component Lsel RMS voltage fundamental component Lsel Distortion factor THD Total Harmonic Distortion current Lsel Distortion...

Page 37: ...x Overvoltage Lx Overcurrent Lx The following values are shown only in WAGO I O CHECK and in CODESYS function blocks not in the process image Active power total Reactive power total Apparent power tot...

Page 38: ...CK or parameters 37 38 and 39 Peak values for current and voltage can also be recorded for a selectable phase The specified observation interval for this can be set using the number of half waves WAGO...

Page 39: ...S2 S3 These calculations are only performed in WAGO I O CHECK and CODESYS function blocks and cannot be exported through the process image Calculation of Energy Time based integration of power yields...

Page 40: ...PI 2 147 483 646 21 474 836 460 kVARh Due to the scaling setting an overflow of the internal meter can occur here as it can only count to a maximum of 9 999 999 999 kVARh However the value in the PI...

Page 41: ...odule always yields the RMS values for current and voltage of the fundamental component for the selected phase It also provides the total harmonic distortion THD for current and voltage From the 40 up...

Page 42: ...into account i e the fundamental component and the upper harmonics LF sign Q P S Positive plus sign positive reactive power Negative minus sign negative reactive power Jump of LF power factor from 1...

Page 43: ...ach phase WAGO I O CHECK or registers 36 37 and 38 and parameters 12 13 14 and 23 31 Signaling is carried out in the process image PI Pos 59 2 Serie 750 WAGO I O SYSTEM Funktionsbeschreibung Funktions...

Page 44: ...age by setting the corresponding bits in Expanded status word 1 byte 2 The clipping limit is 13 93 kVRMS for the voltage inputs 493 1 ARMS for the current inputs 2 The I O module is designed for opera...

Page 45: ...65 Hz and its integer harmonics are calculated Upper harmonic components in the current curve shapes for measured voltages and currents with non integer multiples of the fundamental frequency can aff...

Page 46: ...The I O module provides the fieldbus coupler controller 24 bytes of input and output process data via one logical channel This consists of 8 byte control status words and 16 byte data words The proces...

Page 47: ...2 Output and Input Data Byte Output Data Input Data 0 Control word Status word 1 2 Expanded control word 1 Expanded status word 1 3 4 Expanded control word 2 Expanded status word 2 5 6 Expanded contro...

Page 48: ...OM Communication mode 0 process data communication 1 register communication RES reserved Byte 1 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 2 bit Bit 1 Bit 0 STAT STAT Status query for 0 status phase L1 1 status ph...

Page 49: ...of the measured value from the collection COL_ID which is delivered with process value 2 of the input data Expanded control word 3 Byte 6 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 2 bit Bit 1 Bit 0 MET_ID_3 MET_I...

Page 50: ...Definition of the Status Words Status word Byte 0 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 2 bit Bit 1 Bit 0 COM ERROR ERR_BK ERR_L3 ERR_L2 ERR_L1 COM Communication mode 0 process data communication 1 register...

Page 51: ...1 Range limiting process value 1 0 OK 1 the measured value shown in process value 1 is situated outside the defined value range OVER_2 Range limiting process value 2 0 OK 1 the measured value shown in...

Page 52: ...d not correct counterclockwise STAT5 If STAT_SEL status of Lx L1 L2 L3 Threshold value overcurrent Lx 0 threshold value not reached 1 threshold value reached or exceeded If STAT_SEL status of I O modu...

Page 53: ...to underrun of the required input nominal voltage at Lx If STAT_SEL status of I O module No significance Byte 3 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 2 bit Bit 1 Bit 0 COL_ID_SEL COL_ID_SEL Index of the sele...

Page 54: ...Bit 3 Bit 2 Bit 1 Bit 0 MET_ID_2_SEL MET_ID_2_SEL ID of the measured value from the collection COL_ID_SEL which is in process value 2 of the input data Expanded status word 3 Byte 6 Bit 7 Bit 6 Bit 5...

Page 55: ...L from the collection COL_ID_SEL which is in process value 1 of the input data the format of the 32 bit measured values is defined in the section Measured Value Collections Byte 9 Bit 7 Bit 6 Bit 5 Bi...

Page 56: ...COL_ID_SEL which is in process value 2 of the input data the format of the 32 bit measured values is defined in the section Measured Value Collections Byte 13 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1...

Page 57: ...L_ID_SEL which is in process value 3 of the input data the format of the 32 bit measured values is defined in the section Measured Value Collections Byte 17 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 B...

Page 58: ...COL_ID_SEL which is in process value 4 of the input data the format of the 32 bit measured values is defined in the Section Measured Value Collections Byte 21 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1...

Page 59: ...during the harmonic analysis for phase L2 COL_ID 022 Harmonic analysis L3 All measured values provided by the I O module during the harmonic analysis for phase L3 The individual measured values are id...

Page 60: ...L 4 0x06 MET_ID_1 0x06 MET_ID_1_SEL 5 0x03 MET_ID_2 0x03 MET_ID_2_SEL 6 0x4E MET_ID_3 0x4E MET_ID_3_SEL 7 0x17 MET_ID_4 0x17 MET_ID_4_SEL 8 RMS voltage L3 N 7 0 9 RMS voltage L3 N 15 8 10 RMS voltage...

Page 61: ...004 Total harmonic distortion THD for fundamental component or harmonic distortion HD for voltage upper harmonic MET_ID_2 MET_ID_3 and MET_ID_4 are then used to select the upper harmonic MET_ID_x 1 4...

Page 62: ...3 0x64 MET_ID_3_SEL 7 0x25 MET_ID_4 0x25 MET_ID_4_SEL 8 Measured value type distortion current 7 0 0x03 9 Measured value type distortion current 15 8 0x00 10 Measured value type distortion current 23...

Page 63: ...ge signal at phase L1 is outside the range measurable by the I O module and has been clipped In addition byte 1 is at 0x80 This means that the measured values of the collection are not yet stable The...

Page 64: ...to 2 147 483 646 2 147 483 647 5 5 1 Collection 010 AC Measured Values Table 24 Measured Values of Collection 010 in the Process Image MET_ID Measured Value PI Data Type PI Scaling Factor Voltage 004...

Page 65: ...042 Arithmetic mean current L3 UInt32 0 0001 A 094 Peak value current L1 UInt32 0 0001 A 095 Peak value current L2 UInt32 0 0001 A 096 Peak value current L3 UInt32 0 0001 A Power 007 Active power L1 I...

Page 66: ...energy inductive L1 UInt32 080 Reactive energy inductive L2 UInt32 081 Reactive energy inductive L3 UInt32 082 Reactive energy capacitive L1 UInt32 083 Reactive energy capacitive L2 UInt32 084 Reacti...

Page 67: ...angle phi L2 UInt32 0 01 degrees 021 Phase angle phi L3 UInt32 0 01 degrees 022 cos phi L1 Int32 0 01 023 cos phi L2 Int32 0 01 024 cos phi L3 Int32 0 01 Power Factor 025 PF power factor L1 Int32 0 0...

Page 68: ...t32 0 01 V 003 Distortion current L1 UInt32 0 01 004 Distortion voltage L1 UInt32 0 01 100 Fundamental component L1 depends on selected variable 1 40 Upper harmonic component L1 1st 40th upper harmoni...

Page 69: ...alues for Voltage Process value 0x00119E8C 1 154 700 PI Scaling Factor 0 01 V Formula Measured value process value PI scaling factor Measured value for voltage 11 547 V Calculation of the Measured Val...

Page 70: ...rrent 300 A Active Power Process value 0x14A5CC10 346 410 000 PI Scaling Factor 0 01 W Formula Measured value process value PI scaling factor Measured value for power 3 464 100 W Active Energy Registe...

Page 71: ...alte Struktur Sicherheits und sonstige Hinweise Vorsicht Vorsicht Verletzungsgefahr durch scharfkantige Messerkontakte 6 mod_1256193279401_21 docx 43414 1 Risk of injury due to sharp edged blade cont...

Page 72: ...ding to the project design Errors in the design of the node in terms of the potential groups connection via the power contacts are recognized as the I O modules with power contacts blade contacts cann...

Page 73: ...mod_1264428115588_21 docx 48610 1 Do not touch hot surfaces The surface of the housing can become hot during operation If the device was operated at high ambient temperatures allow it to cool off bef...

Page 74: ...wer contacts if any to the head station or to the preceding and if applicable following I O module are established Pos 80 Serie 750 WAGO I O SYSTEM Montieren Demontieren I O Modul entfernen neutrales...

Page 75: ...g paths The N connection represents the device internal reference potential for all electrical measurements Unwanted additional potential differences between the N connection and the current connectio...

Page 76: ...ay from devices in the cabinet or housing Figure 14 Cable Shield at Ground Potential Improve shielding performance by placing the shield over a large area Higher shielding performance is achieved via...

Page 77: ...re equipped with shield clamps Only then you can ensure that the accuracy and interference immunity specified for the respective I O module can be achieved even in the presence of interference acting...

Page 78: ...be connected to each CAGE CLAMP Do not connect more than one conductor at one single connection If more than one conductor must be routed to one connection these must be connected in an up circuit wi...

Page 79: ...per IEC 60044 7 new version IEC 61869 7 and current sensors per IEC 60044 8 new version IEC 61869 8 and do so in accordance with the information in the section Technical Data Do not confuse the curre...

Page 80: ...ction Schematic for Voltage and Current Measurement Using Voltage Current Sensors No Explanation 1 Generator Distribution transformer e g vector group Dy5 with star point grounding 2 Loads with impeda...

Page 81: ...O CHECK software for Windows For this purpose the fieldbus coupler controller of the node is connected to the USB port of a PC using the WAGO USB communication cable item no 759 923 759 923 000 001 f...

Page 82: ...ce To display the node on the PC connect both using the USB communication cable and launch WAGO I O CHECK The node is displayed Figure 17 WAGO I O CHECK User Interface Node with I O Module Example Rig...

Page 83: ...Phase POM 20KV 300A XTR Manual Version 1 0 0 The dialog appears Figure 18 3 Phase Power Measurement Module Dialog The dialog contains the following sections Start ribbon 1 Measured Value Views menu 2...

Page 84: ...r 3 as a CSV file In this window enter a file name and select the storage location See the section Appendix for examples Settings Opens the settings dialog Calibration Opens the calibration dialog WAG...

Page 85: ...ar Connection status of the I O module IP address of the fieldbus coupler controller or name of the COM port In addition the following error messages are shown for each phase if applicable NoZeroPoint...

Page 86: ...10 3 Phase POM 20KV 300A XTR Manual Version 1 0 0 8 1 5 Settings Dialog In the Settings dialog you can adjust the user settings and I O module parameters To open the dialog click Settings in the Start...

Page 87: ...at you saved previously e g when configuring another I O module from your hard drive You can edit these settings further and finish by saving them in the I O module with Save Note Energy values are di...

Page 88: ...rement units 10 3 milli 100 1 103 kilo 106 mega only for power and energy These settings are saved on the connected PC but not in the I O module You can set the decimal prefixes of the measurement uni...

Page 89: ...ete This action is performed immediately For Energy select the desired scaling factor from the list field The energy values are transferred to the process data with the configured scaling If necessary...

Page 90: ...90 Commissioning WAGO I O System 750 XTR 750 495 040 010 3 Phase POM 20KV 300A XTR Manual Version 1 0 0 Figure 21 Module Tab...

Page 91: ...t the overvoltage threshold and the undercurrent threshold If this value is not reached or is exceeded an error bit is set in the status byte of the process image and a red error LED is enabled Also s...

Page 92: ...opulate them by selecting the meter in question in the list field entering a value in milliwatt hours and clicking Save After this is set the energy metering starts from this value setting 15 meters c...

Page 93: ...WAGO I O System 750 XTR Commissioning 93 750 495 040 010 3 Phase POM 20KV 300A XTR Manual Version 1 0 0 Figure 23 Energy Tab...

Page 94: ...tall the plug in for the 3 Phase Power Measurement Module This resets the password to the initial password List of the factory settings You can find a list of the factory settings in Appendix Factory...

Page 95: ...50 XTR Commissioning 95 750 495 040 010 3 Phase POM 20KV 300A XTR Manual Version 1 0 0 Figure 24 Factory Settings Tab Pos 95 Dokumentation allgemein Gliederungselemente Seitenwechsel 3 mod_12211080450...

Page 96: ...view continuously displays the measured values of all 3 phases These are A sum view of the 3 phases with active reactive and apparent power PF power factor and active reactive and apparent energy A 4...

Page 97: ...red Values view offers detailed displays of the measured values of the corresponding phase including minimum maximum average and peak values Current Phase voltage Line to line voltage Active power Rea...

Page 98: ...shows all currents voltages phase angles and frequencies of the 3 phases together including minimum maximum average and peak values Current Phase voltage Line to line voltage Phase angle Frequency Fig...

Page 99: ...ers View The Powers view shows the active reactive and apparent power of all 3 phases the minimum and maximum values for active power the power factors and the 4 quadrant displays Active power Reactiv...

Page 100: ...3 phases the Energies view shows the active energy values with import and export the reactive energy values with the inductive and capacitive portions and the values for apparent energy that has been...

Page 101: ...3 phases When this view is selected the Analysis context tab next to Start opens here you can select either the diagram view or table view You can also select the phase to analyze and the measured qua...

Page 102: ...ic and 3 selectable upper harmonics of the selected phase the Table View displays Current Harmonic distortion THD and HD current Voltage Harmonic distortion THD and HD voltage As long as the selection...

Page 103: ...fy the duration through the start and end time or enter the number of samples Furthermore you can set a measurement interval sample rate of 250 300 000 ms When the arrow is clicked the 3 Start buttons...

Page 104: ...mation View The Information view shows the item number the designation of the I O module the number of the firmware version software version and the number of the hardware version Figure 33 Measured V...

Page 105: ...llowing before an update Ensure that communication with the fieldbus coupler controller is not interrupted during the update process Damage to I O module if update interrupted During the update proces...

Page 106: ...messages and the parameter settings Table 27 CSV File Snapshot I O Check 3 Phase Power Measurement Measured Values Total active power 10320000 W Total reactive power 50700 var Total apparent power 103...

Page 107: ...310 8 A Peak value current L1 426 4 A Average voltage rms L1 N 0 V Average voltage rms L2 N 0 V Average voltage rms L3 N 0 V Minimum voltage rms L1 N 0 V Minimum voltage rms L2 N 0 V Minimum voltage r...

Page 108: ...00 varh Reactive energy capacitive L2 200 varh Reactive energy capacitive L3 100 varh Reactive energy inductive L1 748300 varh Reactive energy inductive L2 50100 varh Reactive energy inductive L3 5140...

Page 109: ...rent voltage Parameters phase L1 Overvoltage limit 2100 V Overcurrent limit 5000 A Interval observation arithm mean calculation 60 s Interval observation peak value measurement 10 half waves Take curr...

Page 110: ...Parameters Phase L3 Overvoltage limit 2100 V Overcurrent limit 5000 A Interval observation arithm mean calculation 60 s Interval observation peak value measurement 10 half waves Take current transfor...

Page 111: ...wer Measurement Voltage rms L1 N 2019 10 02 09 48 14 11554 2019 10 02 09 48 15 11556 2019 10 02 09 48 15 11559 2019 10 02 09 48 16 11557 2019 10 02 09 48 16 11553 2019 10 02 09 48 17 11550 2019 10 02...

Page 112: ...I O SYSTEM Anhang Werkseinstellungen Default 750 495 040 010 35 mod_1561047932896_21 docx 548705 1 The following values in the registers and parameters are factory settings Table 29 Factory Settings R...

Page 113: ...0x000A 10 half waves P20 R44 0x000A 10 half waves P21 R45 0x000A 10 half waves P22 R46 0x003C 60 s P23 0x5208 21 000 V P24 0x5208 21 000 V P25 0x5208 21 000 V P26 P27 0x02FA F080 5000 A P28 P29 0x02FA...

Page 114: ...rt phase 1 0x3C Energy meter preset active energy import phase 2 0x3D Energy meter preset active energy export phase 2 0x3E Energy meter preset active energy import phase 3 0x3F Energy meter preset ac...

Page 115: ...s data has been received for 100 ms the watchdog is triggered and the LED is deactivated factory setting 1 The watchdog is deactivated and the green RUN LED A remains lit Bit 3 Nominal frequency selec...

Page 116: ...kVARh kVAh factory setting 7 10 kWh kVARh kVAh 8 100 kWh kVARh kVAh 9 1 MWh MVARh MVAh Table 35 Register 36 Register 36 Undervoltage Limit Phase 1 Function Data Type Access Factory Setting Undervolta...

Page 117: ...on interval peak value measurement phase 2 UINT R W 0x000A 0 5 not permitted 6 254 Number of half waves for measuring peak values 255 not permitted Table 40 Register 45 Register 45 Observation Interva...

Page 118: ...eterization error Table 43 Register 48 Register 48 Container 1 Function Data Type Access Factory Setting Container 1 for energy meter and calibration preset UINT R W 0x0000 Table 44 Register 49 Regist...

Page 119: ...ting Container 6 for energy meter and calibration preset UINT R W 0x0000 Table 49 Register 54 Register 54 Container 7 Function Data Type Access Factory Setting Container 7 for energy meter and calibra...

Page 120: ...The main image of the calibration data is OK 1 The main image of the calibration data was restored CRC16 error Bit 9 energy meter 0 The energy meter is OK 1 The energy meter was restored CRC16 error B...

Page 121: ...rvoltage Limit Phase 2 Function Data Type Access Factory Setting Corresponds to register 37 see section Register Assignment Table 56 Parameter 14 Parameter 14 Undervoltage Limit Phase 3 Function Data...

Page 122: ...vervoltage threshold check is disabled 1 Value of the overvoltage threshold Table 63 Parameter 25 Parameter 25 Overvoltage Threshold Value Phase 3 Function Data Type Access Factory Setting Overvoltage...

Page 123: ...lated over 30 seconds 4 The arithmetic mean is calculated over 60 seconds 5 The arithmetic mean is calculated over 300 seconds 6 The arithmetic mean is calculated over 480 seconds 7 The arithmetic mea...

Page 124: ...nds 8 The arithmetic mean is calculated over 900 seconds 9 reserved Table 70 Parameter 37 Parameter 37 Interval Autom Reset Min Max Values Phase 1 Function Data Type Access Factory Setting Time consta...

Page 125: ...old Reactive Energy Function Data Type Access Factory Setting Reactive power threshold above which the active power is metered UINT R W 0x0000 disabled 0 The NOLOAD threshold is disabled factory setti...

Page 126: ...e I O Module Example 74 Figure 14 Cable Shield at Ground Potential 76 Figure 15 Connecting a Conductor to a CAGE CLAMP 78 Figure 16 Connection Schematic for Voltage and Current Measurement Using Volta...

Page 127: ...Technical Data Mechanical Conditions 29 Table 18 Technical Data Climatic Environmental Conditions 29 Table 19 Climatic and Mechanical Environmental Conditions and Shipbuilding 31 Table 20 EMC Immunity...

Page 128: ...e 59 Parameter 21 121 Table 60 Parameter 22 122 Table 61 Parameter 23 122 Table 62 Parameter 24 122 Table 63 Parameter 25 122 Table 64 Parameters 26 and 27 122 Table 65 Parameters 28 and 29 122 Table...

Page 129: ...750 XTR 129 750 495 040 010 3 Phase POM 20KV 300A XTR Manual Version 1 0 0 Pos 113 Dokumentation allgemein Einband Einband Leerseite f r durch 2 teilbare Seitenzahl Standarddruck 3 mod_1219230851078_...

Page 130: ...ente CI 2017 28 mod_1486477503580_21 docx 405394 1 WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 49 571 887 0 Fax 49 571 887 844169 E Mail info wago c...

Reviews: