WAGO I/O System 750 XTR
Appendix 115
750-495/040-010 3-Phase POM 20KV 300A XTR
Manual
Version 1.0.0
Table 32: Register 5
Register 5 – “Response” Command Interface
Function
Data Type
Access
Factory Setting
"Response” Command Interface
UINT
R
0x0000
High byte
Sequence number (Session ID)
Low byte
Response
Request
A mirror image of the request command is created when the command is
successfully applied
0xF0
Command is valid, but cannot be executed
0xFD
The session ID received by the master does not correspond to the last confirmed
session ID + 1
0xFE
The command received by the master is not implemented in the slave
0xFF
General internal error
Table 33: Register 32
Register 32 – Feature Register
Function
Data Type Access
Factory Setting
Feature Register
Flags
R/W
0x0000
Bit 0: Rotary field diagnostics
0:
Rotary field detection is enabled (factory setting)
1
Rotary field detection is disabled
Bit 1: -reserved-
Bit 2: Activation of the RUN LED/watchdog timer
0:
The watchdog is activated, and the green RUN LED “A” lights up. If no process data
has been received for 100 ms, the watchdog is triggered, and the LED is deactivated
(factory setting)
1:
The watchdog is deactivated, and the green RUN LED “A” remains lit.
Bit 3: Nominal frequency selection
0:
The nominal frequency is 50 Hz (factory setting)
1:
The nominal frequency is 60 Hz
Bit 4 + 5: -reserved-
Bit 6 + 7: phase selection for peak value measurement
00:
Peak value measurement for phase 1 is active (factory setting)
01:
Peak value measurement for phase 2 is active
10:
Peak value measurement for phase 3 is active
11 … 15:
-reserved-
Bit 8: Activation of automatic reset of min/max values for phase 1
0:
Automatic deletion of minimum and maximum current, voltage and power values is
disabled (factory setting)
1:
Automatic deletion of minimum and maximum current, voltage and power values is
enabled
Bit 9: activation of automatic reset of min/max values for phase 2
0:
Automatic deletion of minimum and maximum current, voltage and power values is
disabled (factory setting)
1:
Automatic deletion of minimum and maximum current, voltage and power values is
enabled
Bit 10: activation of automatic reset of min/max values for phase 3
0:
Automatic deletion of minimum and maximum current, voltage and power values is
disabled (factory setting)