116 Appendix
WAGO I/O System 750 XTR
750-495/040-010 3-Phase POM 20KV 300A XTR
Manual
Version 1.0.0
Table 33: Register 32
Register 32 – Feature Register
Function
Data Type Access
Factory Setting
Feature Register
Flags
R/W
0x0000
1:
Automatic deletion of minimum and maximum current, voltage and power values is
enabled
Bit 11: -reserved-
Table 34: Register 35
Register 35 – Scaling Factor for Energy Values
Function
Data Type Access
Factory Setting
Scaling factor for energy values
UINT
R/W
0x0006
0:
1 mWh/VARh/VAh
1:
10 mWh/mVARh/mVAh
2:
100 mWh/mVARh/mVAh
3:
1 Wh/VARh/VAh
4:
10 kWh/VARh/VAh
5:
100 kWh/VARh/VAh
6:
1 kWh/kVARh/kVAh (factory setting)
7:
10 kWh/kVARh/kVAh
8:
100 kWh/kVARh/kVAh
9:
1 MWh/MVARh/MVAh
Table 35: Register 36
Register 36 – Undervoltage Limit, Phase 1
Function
Data Type Access
Factory Setting
Undervoltage limit, phase 1,
Resolution: 1 V
UINT
R/W
0x0000 (disabled)
0:
The undervoltage limit check is disabled
≥
1:
Undervoltage limit value
Table 36: Register 37
Register 37 – Undervoltage Limit, Phase 2
Function
Data Type Access
Factory Setting
Undervoltage limit, phase 2,
Resolution: 1 V
UINT
R/W
0x0000 (disabled)
0:
The undervoltage limit check is disabled
≥
1:
Undervoltage limit value
Table 37: Register 38
Register 38 – Undervoltage Limit, Phase 3
Function
Data Type Access
Factory Setting
Undervoltage limit, phase 3,
Resolution: 1 V
UINT
R/W
0x0000 (disabled)
0:
The undervoltage limit check is disabled
≥
1:
Undervoltage limit value