Parameters of the analog inputs can be configured in the parameter group [144] (page 76).
MENU \ DIAGNOSTICS \ INPUTS AND OUTPUTS \ AIN
Name
[ID]
Description
Dim.
AIN1
[256]
Value of the signal brought to the analog input terminals X1:11 and - X1:12 in physical units.
Using the parameter AIN1 Signal [251] (page 77) select the quantity that will be changed
according to the analog input level change.
Parameters of the analog input can be configured in the parameter group [147] (page 76).
V
AIN1
Rel.
[41]
Relative value of the signal connected to the analog input ter X1:11 and - X1:12.
Parameters of the analog input can be configured in the parameter group [147] (page 76).
%
AIN2
[280]
Value of the signal brought to the analog input terminals X1:13 and - X1:14 in physical units.
Using the parameter AIN2 Signal [259] (page 78) select the quantity that will be changed
according to the analog input level change.
Parameters of the analog input can be configured in the parameter group [149] (page 77).
V
AIN2
Rel.
[43]
Relative value of the signal connected to the analog input ter X1:13 and - X1:14.
Parameters of the analog input can be configured in the parameter group [149] (page 77).
%
AIN3
[281]
Value of the signal brought to the analog input terminals X1:15 and - X1:16 in physical units.
Using the parameter AIN3 Signal [269] (page 79) select the quantity that will be changed
according to the analog input level change. Not available for the UNIFREM 400 M converters.
Parameters of the analog input can be configured in the parameter group [148] (page 78).
V
AIN3
Rel.
[44]
Relative value of the signal connected to the analog input ter X1:15 and - X1:16. Not
available for the UNIFREM 400 M converters.
Parameters of the analog input can be configured in the parameter group [148] (page 78).
%
AIN4
[282]
Value of the signal brought to the analog input terminals X1:17 and - X1:18 in physical units.
Using the parameter AIN4 Signal [275] (page 80) select the quantity that will be changed
according to the analog input level change. Not available for the UNIFREM 400 M converters.
Parameters of the analog input can be configured in the parameter group [152] (page 79).
V
AIN4
Rel.
[45]
Relative value of the signal connected to the analog input ter X1:17 and - X1:18. Not
available for the UNIFREM 400 M converters.
Parameters of the analog input can be configured in the parameter group [152] (page 79).
%
4.3.3 RELAYS
Group of parameters number [217]
MENU \ DIAGNOSTICS \ INPUTS AND OUTPUTS \ RELAYS
Name [ID]
Description
Dim.
Relay [185]
Condition of the output relays. Filled rectangle represents the RELEx physical switch-on.
□ RELAY1
Condition of the 1st output relay.
□ RELAY2
Condition of the 2nd output relay.
□ RELAY3
Condition of the 3rd output relay. Not available for the converters UNIFREM 400 M.
4.3.4 AOUT
Group of parameters number [700]
Diagnostic group of quantities for the analog inputs of the converter AOUT1 to AOUT3.
MENU \ DIAGNOSTICS \ INPUTS AND OUTPUTS \ AOUT
Name
[ID]
Description
Dim.
AO1
[701]
Recalculated value of the signal on the analog input terminals X1:19 and X1:20 (X1:15 and
X1:16 for UNIFREM 400 M). Using the parameter AO1 Signal [359] (page 83), select the
quantity according to which the analog output level is changed.
Parameters of the analog input can be configured in the parameter group [370] (page 82).
A
AO2
[702]
Recalculated value of the signal on the analog input terminals X1:21 and X1:22 (X1:17 and
X1:16 for UNIFREM 400 M). Using the parameter AO2 Signal [364] (page 83), select the
quantity according to which the analog output level is changed.
Parameters of the analog input can be configured in the parameter group [371] (page 83).
A