UNIFREM v.3.41x
10 May 2017
Page 37 from 180
7.1.3 Setting the motor data, application and command macro
Begin
Step 4
–
Command macro
Command macro select ion:
Control panel
preset freq.
AIN freq.
MODBUS
PROFIBUS
Up/down commands
Pressure regulation (bar)
Factory settings restored.
Step 1
–
Factory settings
Start source (194)
Source of freq. setpoint (706)
Setpoint frequency (344)
Freq. reverse source (195)
Reset source (704)
Value 0 (220)
Value 1 (239)
Value 2 (245)
Value 3 (293)
Bit1 DS source (552)
Bit2 DS source (555)
Bit3 DS source (558)
Command macro
preset freq
appli ed?
Command macro
Up/
down commands
appli ed?
MP slope (979)
Source of up command (971)
Source of down command (974)
YES
Step 2 - MOTOR
Namepl ate data:
Nom. power (357)
Nom. voltage (59)
Nom. current (151)
Nom. frequency (4)
Nom. revolutions (356)
Motor power factor (227)
Motor overloading (27) -self cooling, forced cool ing
Sine filter (SF) (237)
Step 3 - Application macros
Application macro selecti on :
Pump
Fun
Heavy l oad
Compressor
Conveyor/travel
Lift
Part 2
Fault is present?
YES
NIE
Converter is not ready or there is a fault.
Please, solve the probl em.
Exit the quick setup
Optional faults:
Input phase loss(337)
AIN fault (837)
IRC fault mode (535)
Fault is present?
YES
Converter is not ready or there is a fault.
Please, solve the probl em.
NO
Is AIN1-3
Chosen as freq. setpoint
source?
AIN1-3 Type (153/154/268)
YES
Is mechani cal brake
used?
YES
Mech. brake connection
RELAY 1
RELAY 2
RELAY 3
NO
NO
NO
NO
Do you want to reset the
converter to fact ory
sett ings?
YES
NO
YES
First part of the wizard, Basic motor settings, application and command macro
The first step offers the possibility to reset the converter to factory settings. This action is useful
when the inverter was used in the past and its current setting is unknown or untrustworthy.