UNIFREM v.3.41x
10 May 2017
Page 97 from 180
Name [ID]
Description
Def.
(str. 65).
LS3 Track [886]
Range track that the converter allows to pass when activating the limit switch
function set to the Track + Stop type. Both parameters Transmission ratio
[888] (page 47) and Wheel circumference [889] (page 47) need to be set.
0,0000
m
0,0000
m
÷
99000,0000 m
LS3 Source [901]
Limit switch source setting
None
Look choises of parameter's Quick stop source. [986] (page 49)
LS3 Mask [902]
The limit switch command will be active if at least one of the selected binary
inputs or logical blocks will be active.
Look choises of parameter's Bit1 DS mask [553] (page 55)
LS4
Group of parameters number [879]
Fourth limit switch setting
MENU \ SETTINGS \ FUNCTIONS \ LIMIT SWITCHES \ LS4
Name [ID]
Description
Def.
KS4 Type [883]
Limit switch type setting. Configuration possibilities are the same as in LS1
LS1 Type [880] (page 95).
Look choises of parameter's LS1 Type [880] (page 95)
LS4
Frequency
[918]
Maximum frequency restriction value when activation the limit switch function
set to the "Decelerating" type. Decelerating function will be applied only for the
given rotation direction according to the limit switch type.
0,00
Hz
÷
LS4 Torque [1183]
The value of maximum torque during the activation of Limit switch set to
"Weakening". Weakening is activated for positive or negative torque,
according to the "For reverse" value.
0,0 Nm
Min.
8
÷
8
Value depends on the parameter
Source of the torque reverse [922]
(str. 53). For
the choice
„
According to the setpoint value
“
is from -(
(str. 65)), for
(str. 65).
LS4 Track [887]
Range track that the converter allows to pass when activating the limit switch
function set to the Track + Stop type. Both parameters Transmission ratio
[888] (page 47) and Wheel circumference [889] (page 47) need to be set.
0,0000
m
0,0000
m
÷
99000,0000 m
LS4 Source [904]
Limit switch source setting
None
Look choises of parameter's Quick stop source. [986] (page 49)
LS4 Mask [905]
The limit switch command will be active if at least one of the selected binary
inputs or logical blocks will be active.
Look choises of parameter's Bit1 DS mask [553] (page 55)
7.7.3 PROCESS CONTROLLER
Group of parameters number [385]
General process controller is intended for additional control of the selected quantity. Controlled quantity is
selected using the signal specified by PC feedback source [139] (page 98) and its setpoint by Source of PC
setpoint [130] (page 98). Output PC [64] (page 21) is then used as a source of a parameter of output type
SIGNAL (e.g. frequency or torque setpoint).
MENU \ SETTINGS \ FUNCTIONS \ PROCESS CONTROLLER
Name [ID]
Description
Def.
PC Mode [386]
Selection of process controller mode and physical dimension of the output.
Turned
off
Turned off
Process controller is turned off.