![Vonsch Quatrofrem Series Configuration And Diagnostics Download Page 112](http://html1.mh-extra.com/html/vonsch/quatrofrem-series/quatrofrem-series_configuration-and-diagnostics_1049784112.webp)
UNIFREM v.3.41x
10 May 2017
Page 112 from 180
7.9 DISPLAY
Group of parameters number [48]
Selecting the parameters displayed on the control panel.
7.9.1 DISP. QUANT. SETTINGS
Group of parameters number [88]
Displayed quantities settings. Quantities that are displayed in the upper part of the display in the MONITOR,
SETTINGS and DIAGNOSTICS window.
MENU \ SETTINGS \ DISPLAY \ DISP. QUANT. SETTINGS
Name [ID]
Description
Def.
DV 1 [51]
Selecting the first displayed quantity.
[210] Date
Signal
DV 2 [52]
Selecting the second displayed quantity.
[209] Time
Signal
7.9.2 MONITOR SETTING
Group of parameters number [1214]
Displayed quantities settings. Quantities that are displayed in the upper part of the display in the MONITOR,
SETTINGS and DIAGNOSTICS window.
MENU \ SETTINGS \ DISPLAY \ MONITOR SETTING
Name [ID]
Description
Def.
Monitor 1 [53]
Selecting the quantity that will be displayed in the monitor window
in the first row.
[47] Freq. INV
Signal
Monitor 2 [54]
Selecting the quantity that will be displayed in the monitor window
in the second row.
[46] Voltage DC
Signal
Monitor 3 [55]
Selecting the quantity that will be displayed in the monitor window
in the third row.
[42] Current MT
Signal
Monitor 4 [56]
Selecting the quantity that will be displayed in the monitor window
in the fourth row.
[184] Binary inputs
Signal
Monitor 5 [57]
Selecting the quantity that will be displayed in the monitor window
in the fifth row.
[74]
Cooler
temperature
Signal
Timeout
panel
[198]
Setting the communication timeout for the control panel.
100 ms
15 ms ÷ 200 ms
LANGUAGE [231]
Language change.
Slovensky
Slovensky | English
7.10 COMMUNICATION
Group of parameters number [213]
Setting the serial communication of the converter.
MENU \ SETTINGS \ COMMUNICATION
Name [ID]
Description
Def.
Converter
address [234]
Address is used for identification of the device. It is the sum of preset address and
Address shift [1155] (page 112). It is also used for the communication with the control
panel. In case that more converters are connected, every converter has to have unique
address.
1
1 ÷ 99
Address shift
Selection of bits, which create the external address. The weight of the bits is applied by