Name [ID]
Description
Def.
Freq. INV abs.
The output value is taken from Freq. INV abs. [472] (page 16).
MT Current
The output value is taken from Current MT [42] (page 16).
Power
The output value is taken from Power [66] (page 16).
ETP Current
The output value is taken from ETP Current [870] (page 23).
Torque
The output value is taken from Torque [69] (page 16).
Special
The output value is taken from Special signal AOx.
Signal (AO1_A) [360]
Signal value for the analog output level at point A.
0,00 Hz
Signal (AO1_B) [361]
Signal value for the analog output level at point B.
50,00 Hz
AO1_A [941]
Analog output level at point A.
0,00 mA
0,00 mA ÷ 20,00 mA
AO1_B [942]
Analog output level at point B.
20,00 mA
0,00 mA ÷ 20,00 mA
AO1 Signal [359]
Selection of special signal for the analog output.
[472] Freq. INV abs.
Signal
AO2
Group of parameters number [371]
Second analog output is connected to the terminal: Plus - X1:21, Minus - X1:22 (Plus - X1:17, Minus - X1:16
for UNIFREM 400 M).
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ ANALOG OUTPUTS \ AO2
Name [ID]
Description
Def.
AO2 Type [362]
Analog output type. Configuration possibilities are the same as in AO 1 AO1
Type [358] (page 82).
0-20mA
Look choises of parameter's AO1 Type [358] (page 82)
AO2
Source
[1077]
Analog output quantity selection. Configuration possibilities are the same as
in AO 1 AO1 Source [1076] (page 82).
MT Current
Look choises of parameter's AO1 Source [1076] (page 82)
Signal (AO2_A)
[366]
Signal value for the analog output level at point A.
0,00 A
0,00 ÷
I
NK2
4
4
The value depends on the inverter power line. See installation manual.
Signal (AO2_B)
[368]
Signal value for the analog output level at point B.
6,00 A
0,00 ÷
I
NK2
4
4
The value depends on the inverter power line. See installation manual.
AO2_A [945]
Analog output level at point A.
0,00 mA
0,00 mA ÷ 20,00
mA
AO2_B [946]
Analog output level at point B.
20,00 mA
0,00 mA ÷ 20,00
mA
AO2
Signal
[364]
Selection of the signal that will linearly recalculate the analog output.
[42] Current
MT
Signal
AO3
Group of parameters number [372]
Third analog output is connected to the terminal: Plus - X1:23, Minus - X1:24. Not available for the UNIFREM
400 M converters.
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ ANALOG OUTPUTS \ AO3