SPECIAL SETTING AIN4
Group of parameters number [199]
Analog input mapping setting for the selected parameter. Value of this parameter will be affected by the
analog input value.
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ ANALOG INPUTS \ AIN4 \ SPECIAL SETTING AIN4
Name [ID]
Description
Def.
AIN4 Signal [275]
Selection of the signal that will be linearly recalculated according to the analog
input.
-
Signal
Signal
(AIN4_A)
[276]
Signal value for the analog input level at point A.
-
-
÷
-
Signal
(AIN4_B)
[277]
Signal value for the analog input level at point B.
-
-
÷
-
AIN4_A [955]
Analog input level at point A.
0,00 V
0,00 V ÷ 10,00 V
AIN4_B [956]
Analog input level at point B.
10,00
V
0,00 V ÷ 10,00 V
7.6.3 RELAY OUTPUTS
Group of parameters number [146]
Relay outputs setting, which can be used for signalization of discrete values and events of the converter, e.g.
fault, run, setpoint achieved.
Relay 1
Group of parameters number [186]
Relay 1 setting. Relay is connected to the terminals: NC - X2:25, COM - X2:26, NO - X2:27 (NC - X2:24,
COM - X2:25, NO - X2:26 for UNIFREM 400 M).
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ RELAY OUTPUTS \ RELAY 1
Name [ID]
Description
Def.
R1
Source
[697]
Relay switching function setting.
Motor
operation
Motor operation Relay will switch on when the converter is in start (running).
Ready
Relay will switch on when the converter is READY.
Fault
Relay wil switch on when the fault in the converter occurs.
Brake
Relay will switch on when the mechanical brake function is activated, please see [517]
(page 102).
F=zel
Relay will switch on after reaching the setpoint frequency.
Special
Relay will switch on after satisfying the conditions in the submenu SPECIAL SETTING.
R1 switch-on
time [307]
The relay switch-on time delay.
0,00 s
0,00
s
÷
3600,00 s
After establishment of the switch condition, the relay will switch-on after a selected amount
of time.
R1 switch-off
time [308]
The relay switch-off time delay.
0,00 s
0,00
s
÷
3600,00 s
After termination of the switch condition, the relay will switch-off after a selected amount of
time.
R1 Logic [755]
Determines the relay output evaluation mode. The condition will be evaluated
first, then the switch times will be evaluated and the relay logic will be
evaluated last.
Direct
Direct
If the switch conditions are met, the relay will switch on.
Inverted
If the switch conditions are met, the relay will switch off.