Initial Commissioning
The easiest way of doing the initial commissioning is to use the Quick Menu button and follow the quick
set-up procedure using G-LCP (read table from left to right):
Press
Q2 Quick Menu
0-01 Language
Set language
1-20 Motor power
Set motor nameplate power
1-22 Motor voltage
Set nameplate voltage
1-23 Motor frequency
Set nameplate frequency
1-24 Motor current
Set nameplate current
1-25 Motor nominal speed
Set nameplate speed in RPM
5-12 Terminal 27 Digital In-
put
If the terminal default is
Coast inverse,
it is
possible to change this setting to
No func-
tion
. No connection to terminal 27 is then
needed for running AMA
1-29 Automatic Motor Adap-
tation
Set desired AMA function. Enabling complete
AMA is recommended
3-02 Minimum Reference
Set the minimum speed of the motor shaft
3-03 Maximum Reference
Set the maximum speed of the motor shaft
3-41 Ramp1 up time
Set the ramping-up time with reference to
the nominal motor speed (set in par. 1-25)
3-42 Ramp1 down time
Set the ramping-down time with reference to
the nominal motor speed (set in par. 1-25)
3-13 Reference site
Set the site from where the reference must
work
VLT
®
AutomationDrive FC 300 Instruction Manual
How
to
Program
MG.33.A8.22 - VLT
®
is a registered Danfoss trademark.
39