Motor Thermal Protection
The electronic thermal relay in FC 300 has received the UL-approval for single motor protection, when
par. 1-90
Motor Thermal Protection
is set for
ETR Trip
and par. 1-24
Motor current, I
M,N
is set to the
rated motor current (see motor nameplate).
VLT
®
AutomationDrive FC 300 Instruction Manual
How
to
Install
MG.33.A8.22 - VLT
®
is a registered Danfoss trademark.
35