The illustration below shows a Stopping Category 0 (EN 60204-1) with safety Category 3 (EN 954-1).
The circuit interruption is caused by an opening door contact. The illustration also shows how to connect
a non-safety-related hardware coast.
Illustration of the essential aspects of an installation to achieve a Stopping Category 0 (EN 60204-1) with safety Cat-
egory 3 (EN 954-1).
IT Line
Do not connect 400 V adjustable frequency drives with RFI filters to the line supply with a
voltage between phase and ground of more than 440 V.
For IT lines and delta ground (grounded leg), line voltage may exceed 440 V between phase
and ground.
On the FC 302, par. 14-50
RFI 1
can be used to disconnect the internal RFI capacitors from the RFI filter
to ground. If this is done, it will reduce the RFI performance to A2 level.
VLT
®
AutomationDrive FC 300 Instruction Manual