Assembling of IP55 / NEMA Type 12 (A5 housing) with line supply disconnector
The line power switch is placed on the left side on
the B1, B2, C1 and C2 enclosures. The line power
switch on the A5 enclosure is placed on the right
side
Connection Examples
Start/Stop
Terminal 18 = Par. 5-10 [8]
Start
Terminal 27 = Par. 5-12 [0]
No operation
(Default
coast inverse
)
Terminal 37 = Safe stop (FC 302 and FC 301 A1
only)
Pulse Start/Stop
Terminal 18 = Par. 5-10 [9]
Latched start
Terminal 27= Par. 5-12 [6]
Stop inverse
Terminal 37 = Safe stop (FC 302 and FC 301 A1
only)