Switches S201, S202, and S801
Switches S201 (A53) and S202 (A54) are used to select a current (0-20 mA) or a voltage (-10 to 10 V)
configuration for the analog input terminals 53 and 54, respectively.
Switch S801 (BUS TER.) can be used to enable termination on the RS-485 port (terminals 68 and 69).
See drawing
Diagram showing all electrical terminals
in the
Electrical Installation
section
.
Default settings:
S201 (A53) = OFF (voltage input)
S202 (A54) = OFF (voltage input)
S801 (Bus termination) = OFF
When changing the function of S201, S202 or S801, be careful not to force the switch over.
Removing the LCP fixture (cradle) when operating the switches is recommended. The switches
must not be operated while the adjustable frequency drive is powered.
VLT
®
AutomationDrive FC 300 Instruction Manual
How
to
Install
MG.33.A8.22 - VLT
®