Option and default
Configuration Instructions
in 20 hours
confirmation time:
a) A second panic device is activated.
b) A second panic alarm on the same device is activated.
c) A tamper event is activated (not from the zone / device that initiated the panic
alarm).
Options:
in 4
/
8
/
12
/
20
/
24 hours
and
disabled
07:RPT CNFM ALRM
bypass
Define whether the system will report a confirmed alarm.
bypass
- The system will report a confirmed alarm and will bypass all alarmed
open zones when the siren ends or when the confirmation timer expires.
disable
- The system will not report a confirmed alarm.
enable
- The system will report a confirmed alarm.
08:ENTRY DELAY 1
30 seconds
Two different entry delays allow the user to enter the protected site (while the system
is in the armed state) via 2 specific doors and routes without causing an alarm.
Following entry, the user must disarm the control panel before the entry delay expires.
Slow-rate warning beeps start sounding once the door is opened, until the last 10
seconds of the delay, during which the beeping rate increases. Locations No. 1 (entry
delay 1) and 2 (entry delay 2) allow you to program the length of these delays.
09:ENTRY DELAY 2
60 seconds
Options:
10
/
15
/
30
/
45
/
60
seconds
;
3
/
4 minutes
10:ABORT TIME
in 30 seconds
The PowerMaster can be configured to provide a delay before reporting an alarm to
the monitoring station (not applicable to alarms from FIRE, 24H SILENT and
EMERGENCY zones). During this delay period, the siren sounds but the alarm is not
reported. If the user disarms the system within the delay time, the alarm is aborted.
You can activate the feature and select the "Abort Time" interval.
Options:
in 00
/
15
/
30
/
45
/
60
seconds
;
in 2/3
/
4 minutes
11:CANCEL ALARM
in 5 minutes
The PowerMaster can be configured to provide a “Cancel Alarm” time window that
starts upon reporting an alarm to the Monitoring Station. If the user disarms the system
within that "cancel alarm" time, a “cancel alarm” message is sent to the Monitoring
Station indicating that the alarm was canceled by the user.
Options:
in 1
/
5
/
15
/
60
minute/s
;
in 4 hours
and
not active
78
D-306919 KP-250 PG2 Installer’s Guide