Manual VIPA System 200V
Chapter 3 Deployment IM 253DP
HB97E - IM - RE_253-xDPxx - Rev. 12/44
3-35
… Continue
Alarm status at diagnostic alarm Bytes x+8 to x+19
(corresponds CPU diagnostic record set 1)
Byte
Bit 7 ... Bit 0
x+8
70h: Module with digital inputs
71h: Module with analog inputs
72h: Module with digital outputs
73h: Module with analog outputs
74h: Module with analog in-/-outputs
76h: Counter
x+9
Lenght of the channel-specific diagnostic
x+10
Number of channels per module
x+12
Diagnostic event on the channel/channel group 0
Assignment see module description
x+13
Diagnostic event on the channel/channel group 1
Assignment see module description
.
.
.
.
.
.
x+19
Diagnostic event on the channel/channel group 7
Assignment see module description
Alarm status at process alarm Bytes x+4 to x+7
More detailed information to the diagnostic data is to find in the concerning
module descriptions.
Summary of Contents for IM 253 DP Series
Page 1: ...VIPA System 200V IM Manual HB97E_IM RE_253 xDPxx Rev 12 44 November 2012...
Page 4: ...Contents Manual VIPA System 200V ii HB97E IM RE_253 xDPxx Rev 12 44...
Page 8: ...Safety information Manual VIPA System 200V 4 HB97E IM RE_253 xDPxx Rev 12 44...
Page 26: ...Chapter 1 Basics and Assembly Manual VIPA System 200V 1 18 HB97E IM RE_253 xDPxx Rev 12 44...
Page 100: ...Chapter 3 Deployment IM 253DP Manual VIPA System 200V 3 60 HB97E IM RE_253 xDPxx Rev 12 44...