Chapter 3 Deployment IM 253DP
Manual VIPA System 200V
3-28
HB97E - IM - RE_253-xDPxx - Rev. 12/44
IM 253-xDPx1 - DP-V1 slave - Diagnostic functions
PROFIBUS DP provides an extensive set of diagnostic functions for quick
error localization. Diagnostic messages are transferred via the bus and
collected by the master.
At the DP-V1 the device related diagnostic has been improved as further
function and is subdivided into the categories alarms and status messages.
Additionally in the DP-V1 slave from VIPA the last 100 alarm messages are
stored in a RAM res. in the flash with a time stamp and may be evaluated
with a software.
For this, please call the VIPA hotline!
The system also stores diagnostic messages like the states "Ready" res.
"DataExchange" that are not passed on to the master.
With every status change between "Ready" and "DataExchange" the
PROFIBUS slave stores the diagnostic-RAM content in a Flash-ROM and
writes it back to the RAM at every reboot.
With the short setting of 00 at the address lever you may save the
diagnostic data in the Flash-ROM during "DataExchange".
At voltage failure res. decreasing voltage a time stamp is stored in the
EEPROM. If enough voltage is still left, a diagnostic output to the master
occurs.
At the next reboot an undervoltage/shut-down diagnostic message is
generated from the time stamp of the EEPROMs and is stored in the
Diagnostic-RAM.
Overview
Internal diagnostic
system messages
Manual storage of
diagnostic data
Diagnostic
messages at
voltage failure
Summary of Contents for IM 253 DP Series
Page 1: ...VIPA System 200V IM Manual HB97E_IM RE_253 xDPxx Rev 12 44 November 2012...
Page 4: ...Contents Manual VIPA System 200V ii HB97E IM RE_253 xDPxx Rev 12 44...
Page 8: ...Safety information Manual VIPA System 200V 4 HB97E IM RE_253 xDPxx Rev 12 44...
Page 26: ...Chapter 1 Basics and Assembly Manual VIPA System 200V 1 18 HB97E IM RE_253 xDPxx Rev 12 44...
Page 100: ...Chapter 3 Deployment IM 253DP Manual VIPA System 200V 3 60 HB97E IM RE_253 xDPxx Rev 12 44...