Manual VIPA System 200V
Chapter 2 Hardware description
HB97E - IM - RE_253-xDPxx - Rev. 12/44
2-5
IM 253-1DP11 - DP-V1 slave - Structure
•
PROFIBUS (DP-V0, DP-V1)
•
PROFIBUS DP slave for max. 32 peripheral modules
(max. 16 analog modules)
•
Max. 244Byte input data and 244Byte output data
•
Internal diagnostic protocol
•
Integrated DC 24V power supply for the peripheral modules (3.5A max.)
•
Supports all PROFIBUS data transfer rates
•
1 MSAC_C1 connection (Read, Write) with 244Byte data
(4 Byte DP-V1- 240Byte user data)
•
3 MSAC_C2 connections (Initiale, Read, Write, DataTransport,
Initiate Abort) with each 244Byte data
(4 Byte DP-V1- 240 Byte user data)
[1]
LED status indicators
[2] Address
selector
(Coding switch)
[3] FO
interface
[4]
Connector for DC 24V
power supply
Front view
253-1DP11
2
1
4
3
PW
ER
RD
DE
IM 253 DPO
Adr.
X 2
3 4
VIPA 253-1DP11
DC24V
+
-
1
2
IN
OUT
9 9
1
2
+ DC 24 V
0 V
+
-
X1
IN
OUT
1
2
Send
Receive
3
4
Send
Receive
LWL
Properties
IM 253DPO
Use as
DP-V1 slave
Interfaces
Summary of Contents for IM 253 DP Series
Page 1: ...VIPA System 200V IM Manual HB97E_IM RE_253 xDPxx Rev 12 44 November 2012...
Page 4: ...Contents Manual VIPA System 200V ii HB97E IM RE_253 xDPxx Rev 12 44...
Page 8: ...Safety information Manual VIPA System 200V 4 HB97E IM RE_253 xDPxx Rev 12 44...
Page 26: ...Chapter 1 Basics and Assembly Manual VIPA System 200V 1 18 HB97E IM RE_253 xDPxx Rev 12 44...
Page 100: ...Chapter 3 Deployment IM 253DP Manual VIPA System 200V 3 60 HB97E IM RE_253 xDPxx Rev 12 44...