Max. 125 DP slaves at one DP master - max. 32 slaves/segment
•
Max. 16 DPO slaves at one DPO master at 1.5MBaud
•
You can only install or remove peripheral modules when you have
turned the power off!
•
The max. distance for RS485 cables between two stations is 1200m
(depending on the baud rate).
•
The max. distance for FO cables between two stations is 300m (at HCS-
FO) and 50m (at POF-FO).
•
The maximum baud rate is 12MBaud.
•
The PROFIBUS address of operational modules must never be
changed.
PROFIBUS DP provides an extensive set of diagnostic functions for fast
error localization. Diagnostic messages are transferred via the bus and
collected by the master.
As a further function, the device-specific diagnostic of the DP-V1 have been
enhanced and divided into the categories alarms and status messages.
DP-V0
provides the basic functionality of DP, including cycle data
exchange as well as station diagnostic, module diagnostic and channel-
specific diagnostic.
Data is transferred cyclically between the DP master and the DP slave by
means of transmit and receive buffers.
DP-Master
Input
Output
DP-Slave with I/O-Modules
I/O Modules
Communication
Processor
receive buffer
PROFIBUS-DP
V-Bus
send buffer
V-Bus cycle
DP cycle
PII
PIQ
PII: process image of the inputs
PIQ: process image of the outputs
Restrictions
Diagnostic
Function
cyclic data
communication
(DP-V0)
Summary of Contents for IM 253 DP Series
Page 1: ...VIPA System 200V IM Manual HB97E_IM RE_253 xDPxx Rev 12 44 November 2012...
Page 4: ...Contents Manual VIPA System 200V ii HB97E IM RE_253 xDPxx Rev 12 44...
Page 8: ...Safety information Manual VIPA System 200V 4 HB97E IM RE_253 xDPxx Rev 12 44...
Page 26: ...Chapter 1 Basics and Assembly Manual VIPA System 200V 1 18 HB97E IM RE_253 xDPxx Rev 12 44...
Page 100: ...Chapter 3 Deployment IM 253DP Manual VIPA System 200V 3 60 HB97E IM RE_253 xDPxx Rev 12 44...