Module state,
which can be activated by parameterization, you gain
information about the error that occurred at a module.
Note!
Note that the length of the
Module state
of the IM 253-1DP31 - ECO is
limited to 6.
Module state
Byte
Bit 7 ... Bit 0
X
Bit 5 ... 0: 001100 (fix) Length of the Module status*
Bit 7 ... 6: 00 (fix) Code for Module status
X+1
82h (fix) Status type Module status
X+2 00h
(fix)
X+3 00h
(fix)
X+4
Follow bits indicates the status of the modules from slot 1 ... 32
00: Module ok - valid Data
01: Module error - invalid Data (Module defective)
10: Incorrect module - invalid Data
11: No Module - invalid Data
Bit 1, 0: Module status module slot 1
Bit 3, 2: Module status module slot 2
Bit 5, 4: Module status module slot 3
Bit 7, 6: Module status module slot 4
X+5
Bit 1, 0: Module status module slot 5
Bit 3, 2: Module status module slot 6
Bit 5, 4: Module status module slot 7
Bit 7, 6: Module status module slot 8
X+6
Bit 1, 0: Module status module slot 9
Bit 3, 2: Module status module slot 10
Bit 5, 4: Module status module slot 11
Bit 7, 6: Module status module slot 12
X+7
Bit 1, 0: Module status module slot 13
Bit 3, 2: Module status module slot 14
Bit 5, 4: Module status module slot 15
Bit 7, 6: Module status module slot 16
X+8
Bit 1, 0: Module status module slot 17
Bit 3, 2: Module status module slot 18
Bit 5, 4: Module status module slot 19
Bit 7, 6: Module status module slot 20
X+9
Bit 1, 0: Module status module slot 21
Bit 3, 2: Module status module slot 22
Bit 5, 4: Module status module slot 23
Bit 7, 6: Module status module slot 24
X+10
Bit 1, 0: Module status module slot 25
Bit 3, 2: Module status module slot 26
Bit 5, 4: Module status module slot 27
Bit 7, 6: Module status module slot 28
X+11
Bit 1, 0: Module status module slot 29
Bit 3, 2: Module status module slot 30
Bit 5, 4: Module status module slot 31
Bit 7, 6: Module status module slot 32
*)
Bit 5 ... 0: 000110 at 253-1DP31 - ECO
Module state
Summary of Contents for IM 253 DP Series
Page 1: ...VIPA System 200V IM Manual HB97E_IM RE_253 xDPxx Rev 12 44 November 2012...
Page 4: ...Contents Manual VIPA System 200V ii HB97E IM RE_253 xDPxx Rev 12 44...
Page 8: ...Safety information Manual VIPA System 200V 4 HB97E IM RE_253 xDPxx Rev 12 44...
Page 26: ...Chapter 1 Basics and Assembly Manual VIPA System 200V 1 18 HB97E IM RE_253 xDPxx Rev 12 44...
Page 100: ...Chapter 3 Deployment IM 253DP Manual VIPA System 200V 3 60 HB97E IM RE_253 xDPxx Rev 12 44...