HB97E - IM - RE_253-xDPxx - Rev. 12/44
3-17
The following section contains all the messages that the diagnostic data
can consist of. The structure of Byte 2 ... Byte 23 depends on the message
(Byte 0). When the diagnostic data is transferred to the master via
PROFIBUS, Byte 7 of the master corresponds to Byte 0 of the slave. The
specified length represents the "length of the diagnostic data" during the
PROFIBUS data transfer.
DP parameter error
Length: 8
The parameter telegram is too short or too long
Byte
Bit 7 ... Bit 0
0
0Ah: DP parameter error
1
Module no. or slot no.
1 ... 32: module no. or slot no.
0: module no. or slot no. not available
2
Length user parameter data
3 Mode
0: standard mode
1: 400-mode
4
Number of digital modules (slave)
5
Number of analog modules (slave)
6
Number of analog modules (master)
DP configuration error - length
Length: 6
Depending on the mode, the length of the configuration message is
compared to the length of the default configuration (modules detected on
the V-Bus).
Byte
Bit 7 ... Bit 0
0
14h: DP configuration error - length
1
Module no. or slot no.
1 ... 32: module no. or slot no.
0: module no. or slot no. not available
2
Configuration data quantity (master)
4
Configuration data quantity (slave)
3 Mode
0: Standard mode
1: 400-mode
Overview of
diagnostic
messages
0Ah
14h
Summary of Contents for IM 253 DP Series
Page 1: ...VIPA System 200V IM Manual HB97E_IM RE_253 xDPxx Rev 12 44 November 2012...
Page 4: ...Contents Manual VIPA System 200V ii HB97E IM RE_253 xDPxx Rev 12 44...
Page 8: ...Safety information Manual VIPA System 200V 4 HB97E IM RE_253 xDPxx Rev 12 44...
Page 26: ...Chapter 1 Basics and Assembly Manual VIPA System 200V 1 18 HB97E IM RE_253 xDPxx Rev 12 44...
Page 100: ...Chapter 3 Deployment IM 253DP Manual VIPA System 200V 3 60 HB97E IM RE_253 xDPxx Rev 12 44...