Manual VIPA System 200V
Chapter 2 Hardware description
HB97E - IM - RE_253-xDPxx - Rev. 12/44
2-13
Order number
253-1DP31
Type
IM 253DP, PROFIBUS-DP slave
Technical data power supply
Power supply (rated value)
DC 24 V
Power supply (permitted range)
DC 20.4...28.8 V
Reverse polarity protection
9
Current consumption (no-load operation)
50 mA
Current consumption (rated value)
300 mA
Inrush current
60 A
I²t 0.4
A²s
Max. current drain at backplane bus
0.8 A
Max. current drain load supply
-
Power loss
1.5 W
Status information, alarms, diagnostics
Status display
yes
Interrupts yes,
parameterizable
Process alarm
yes, parameterizable
Diagnostic interrupt
yes, parameterizable
Diagnostic functions
yes, parameterizable
Diagnostics information read-out
possible
Supply voltage display
green LED
Service Indicator
-
Group error display
red SF LED
Channel error display
none
Hardware configuration
Racks, max.
1
Modules per rack, max.
8
Number of digital modules, max.
8
Number of analog modules, max.
8
Communication
Fieldbus
PROFIBUS-DP to EN 50170
Type of interface
RS485
Connector
Sub-D, 9-pin, female
Topology
Linear bus with bus termination at
both ends
Electrically isolated
9
Number of participants, max.
125
Node addresses
1 - 125
Transmission speed, min.
9.6 kbit/s
Transmission speed, max.
12 Mbit/s
Address range inputs, max.
244 Byte
Address range outputs, max.
244 Byte
Number of TxPDOs, max.
-
Number of RxPDOs, max.
-
Housing
Material
PPE / PA 6.6
Mounting
Profile rail 35 mm
Mechanical data
Dimensions (WxHxD)
25.4 x 76 x 78 mm
Weight 90
g
Environmental conditions
Operating temperature
0 °C to 60 °C
Storage temperature
-25 °C to 70 °C
Certifications
UL508 certification
yes
253-1DP31
Summary of Contents for IM 253 DP Series
Page 1: ...VIPA System 200V IM Manual HB97E_IM RE_253 xDPxx Rev 12 44 November 2012...
Page 4: ...Contents Manual VIPA System 200V ii HB97E IM RE_253 xDPxx Rev 12 44...
Page 8: ...Safety information Manual VIPA System 200V 4 HB97E IM RE_253 xDPxx Rev 12 44...
Page 26: ...Chapter 1 Basics and Assembly Manual VIPA System 200V 1 18 HB97E IM RE_253 xDPxx Rev 12 44...
Page 100: ...Chapter 3 Deployment IM 253DP Manual VIPA System 200V 3 60 HB97E IM RE_253 xDPxx Rev 12 44...